Chillers deltachill™ air cooled and freecool, Desi gn, Design data – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 54: Glycol, Correction factors

Advertising
background image

54

Chiller Technical Manual 7267818 V1.4.0_04_2014

D

esi

gn

Chillers

DeltaChill™ Air Cooled and FreeCool

Design Data

Glycol

Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be

exposed to freezing temperatures (lower than 3°C Ambient). This is specified further in the environmental consideration

section at the front of this document.

Glycol Percentage / Freezing Point

Temperature °C

0% / 0°C

20% / -7.8°C

25% / -10.7°C

30% / -14.1°C

35% / -17.9°C

40% / -22.3°C

0

4.21

3.77

3.68

3.59

3.50

3.40

5

4.20

3.78

3.69

3.60

3.51

3.42

10

4.19

3.79

3.71

3.62

3.53

3.44

15

4.19

3.80

3.72

3.63

3.54

3.45

20

4.18

3.82

3.73

3.65

3.56

3.47

25

4.18

3.83

3.74

3.66

3.57

3.49

30

4.18

3.84

3.76

3.67

3.59

3.50

35

4.18

3.85

3.77

3.69

3.60

3.52

40

4.18

3.86

3.78

3.70

3.62

3.54

45

4.18

3.87

3.79

3.72

3.63

3.55

Glycol Percentage / Freezing Point

Temperature °C

0% / °C

20% / -7.1°C

25% / -9.6°C

30% / -12.7°C

35% / -16.4°C

40% / -21.1°C

0

999.8

1035.7

1043.7

1051.8

1059.3

1066.8

5

999.9

1034.4

1042.4

1050.3

1057.8

1065.2

10

999.7

1032.9

1040.9

1048.8

1056.1

1063.5

15

999.0

1031.4

1039.2

1047.1

1054.4

1061.7

20

998.2

1029.7

1037.5

1045.3

1052.5

1059.7

25

997.0

1027.9

1035.6

1043.3

1050.5

1057.6

30

995.6

1026.0

1033.6

1041.3

1048.3

1055.4

35

994.0

1024.0

1031.5

1039.1

1046.1

1053.1

40

992.2

1021.8

1029.3

1036.8

1043.7

1050.6

45

990.2

1019.6

1027.0

1034.4

1041.2

1048.1

Ethylene Glycol Specific Heat

Ethylene Glycol Density

Kw =ρ x m x Cp x ∆t

Where

kW = Cooling Performance (KW)

ρ =

Density of cooling medium (kg/m³)

m = mass flow of cooling media (kg/s)

Cp = Specific heat Capacity (kj/kg K)

∆t = Temperature difference between Inlet and Outlet (K)

Glycol in System / Freezing Point ºC

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

Cooling Duty

Catalogue Data x by:

0.98

0.97

0.95

0.93

Input Power

0.99

0.98

0.96

0.95

Water Flow

0.99

1.02

1.04

1.07

Pressure Drop

1.05

1.20

1.38

1.57

Correction Factors