Installation Data

Interconnecting Wiring

DCC / DCF

L1

Mains incoming supply 400V/3PH/50Hz

L2

L3

PE

L4

Separate Permanent Supply 230V/1PH/50Hz

N1

(1)

PE

L4

External Trace Heating Connections

N1

240V/500W max

502

Unit Remote On/Off 24VAC

505

500

(1)

Evaporator Water Flow Switch 24VAC

504

502

(1)

Remote Pump On / Off

515

502

(1)

Remote Pump Interlock

529

500

Remote setpoint adjust

825

573

Non-Critical Alarm

Volt Free Common Alarm

574

Volt Free Alarm N/O

575

Volt Free Alarm N/C

576

Critical Alarm

Volt Free Common Alarm

577

Volt Free Alarm N/O

578

Volt Free Alarm N/C

RX-/Tx-

Use Awg20/22 twisted pair (with overall

shield) cable, Belden ref. 8762 (Airedale

ref: 6110316), or equivalent, for network

RX+/Tx+

Network Connections In

GND

RX-/Tx-

Use Awg20/22 twisted pair (with overall

shield) cable, Belden ref. 8762 (Airedale

ref: 6110316), or equivalent, for network

RX+/Tx+

Network Connections

GND

CAUTION

(1) MUST be directly wired to the chiller to validate warranty.