Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

158

DCC070TX-14GPYY

5

741.9

200.2

701.2

220.8

656.8

244.5

608.7

271.3

6

763.3

201.6

721.6

222.4

675.9

246.1

626.7

272.9

7

785.0

203.1

742.2

224.0

695.3

247.8

644.1

274.8

8

807.0

204.6

763.0

225.6

714.9

249.5

663.1

276.3

9

829.1

206.2

784.1

227.3

734.8

251.2

681.7

278.1

10

851.4

207.8

805.3

228.9

754.8

253.0

700.5

280.0

159

DCC055DX-15DYV0

5

582.2

142.4

553.5

156.7

521.8

173.3

487.3

192.2

6

599.5

143.2

570.1

157.5

537.6

174.1

502.2

193.1

7

616.9

143.9

586.9

158.2

553.6

174.9

517.3

193.9

8

634.6

144.6

603.8

159.0

569.8

175.7

532.6

194.8

9

652.4

145.4

621.0

159.8

586.1

176.5

548.1

195.6

10

670.2

146.1

638.3

160.6

602.7

177.4

563.8

196.5

160

DCC059DX-16DVV0

5

615.7

149.4

585.2

164.4

551.5

181.8

515.0

201.7

6

634.0

150.1

602.7

165.1

568.2

182.5

530.7

202.6

7

652.5

150.8

620.5

165.9

585.2

183.4

546.7

203.4

8

671.3

151.5

638.5

166.7

602.3

184.2

562.9

204.3

9

690.2

152.3

656.8

167.5

619.7

185.0

579.3

205.2

10

709.4

153.0

675.2

168.3

637.3

185.9

596.0

206.1

161

DCC061DX-16DVW0

5

643.3

158.6

611.2

174.2

575.6

192.2

536.8

212.8

6

662.1

159.5

629.3

175.1

592.8

193.2

552.9

213.8

7

681.2

160.3

647.6

176.1

610.2

194.2

569.3

214.8

8

700.4

161.2

666.1

177.0

627.8

195.2

585.9

215.9

9

719.9

162.1

684.8

178.0

645.6

196.2

602.8

217.0

10

739.5

163.0

703.7

178.9

663.7

197.2

619.8

218.1

162

DCC065DX-16DWW0

5

683.4

168.4

648.4

184.7

609.7

203.2

567.5

224.4

6

703.3

169.5

667.5

185.8

627.7

204.4

584.3

225.6

7

723.4

170.5

686.7

186.9

645.9

205.6

601.4

226.8

8

743.7

171.5

706.2

188.0

664.4

206.8

618.7

228.1

9

764.3

172.6

725.8

189.2

683.1

208.1

636.3

229.4

10

785.0

173.7

745.7

190.4

701.9

209.3

654.1

230.7

163

DCC068TX-16GPPY

5

726.0

182.1

687.8

200.1

645.9

220.8

600.5

244.3

6

747.3

183.3

708.2

201.4

665.1

222.1

618.4

245.6

7

769.0

184.4

728.8

202.6

684.5

223.4

636.6

247.0

8

790.8

185.6

749.6

203.9

704.3

224.8

655.1

248.4

9

812.9

186.9

770.7

205.2

724.2

226.2

673.8

249.8

10

835.2

188.1

792.1

206.6

744.4

227.6

692.8

251.3

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.