192

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

134

DCC088TR-18GVVW

5

927.8

236.8

884.0

261.6

835.8

290.3

782.7

322.8

6

956.2

238.5

911.1

263.3

861.7

292.0

807.0

324.5

7

984.7

240.2

939.1

265.1

888.1

293.8

831.7

326.2

8

1013.3

241.7

966.6

266.8

914.8

295.7

856.8

328.0

9

1042.6

243.4

995.0

268.6

942.0

297.5

882.4

329.8

10

1072.2

245.1

1023.7

270.4

969.6

299.4

908.4

331.6

135

DCC091TR-18GVWW

5

959.1

247.0

914.4

272.5

864.3

301.8

809.1

334.9

6

988.6

249.0

942.2

274.4

890.9

303.7

833.6

336.6

7

1017.8

250.8

970.7

276.4

917.9

305.7

858.6

338.4

8

1046.9

252.5

999.1

278.3

945.3

307.7

884.0

340.2

9

1076.9

254.3

1028.1

280.2

973.2

309.8

909.8

342.1

10

1107.3

256.2

1057.5

282.2

1001.4

311.8

936.0

344.0

136

DCC094TR-18GWWW

5

990.5

257.2

944.8

283.4

892.9

313.3

835.4

346.9

6

1021.0

259.4

973.3

285.5

920.1

315.4

860.2

348.7

7

1050.9

261.4

1002.3

287.6

947.7

317.6

885.5

350.6

8

1080.5

263.2

1031.6

289.7

975.8

319.8

911.1

352.5

9

1111.2

265.2

1061.3

291.9

1004.3

322.0

937.2

354.4

10

1142.3

267.2

1091.3

294.0

1033.2

324.3

963.6

356.4

137

DCC082TR-19GYYV

5

847.1

207.7

807.8

230.0

763.2

255.4

715.5

284.6

6

872.9

209.0

832.6

231.3

787.6

257.0

738.1

286.0

7

899.0

210.3

857.9

232.7

811.8

258.4

760.9

287.4

8

925.4

211.7

883.4

234.1

835.9

259.7

784.4

288.9

9

952.2

213.1

909.4

235.5

860.9

261.1

808.2

290.4

10

979.3

214.5

935.6

236.9

886.2

262.6

832.5

292.0

138

DCC084TR-20GYVV

5

872.0

213.7

831.7

236.8

786.5

263.1

737.3

293.3

6

898.4

215.0

857.2

238.1

811.2

264.6

760.5

294.8

7

925.1

216.3

883.1

239.4

836.0

266.0

783.7

296.1

8

952.2

217.6

909.3

240.8

861.0

267.4

807.8

297.6

9

979.6

219.0

935.9

242.2

886.5

268.8

832.2

299.1

10

1007.3

220.3

962.8

243.6

912.5

270.3

857.1

300.7

139

DCC087TR-21GVVV

5

896.9

219.8

855.7

243.5

809.8

270.9

759.2

302.1

6

923.9

221.0

881.8

244.9

834.7

272.2

783.0

303.5

7

951.2

222.3

908.3

246.2

860.2

273.6

806.4

304.7

8

979.0

223.6

935.2

247.6

886.1

275.1

831.1

306.2

9

1007.0

224.9

962.4

248.9

912.2

276.5

856.3

307.8

10

1035.3

226.2

989.9

250.3

938.8

278.0

881.8

309.3

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

DCC Performance Data EC Fans

Advertising