Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 178: Dcc performance data ac fans

Advertising
background image

178

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

134

DCC088TR-18GVVW

5

934.4

242.2

887.0

265.3

833.9

292.5

776.2

323.6

6

962.2

243.6

913.5

266.8

859.0

294.0

799.6

325.2

7

990.3

244.9

940.3

268.3

884.4

295.6

823.4

326.8

8

1018.8

246.3

967.5

269.8

910.1

297.2

847.6

328.5

9

1047.6

247.8

995.0

271.4

936.2

298.9

872.1

330.2

10

1076.7

249.2

1022.8

272.9

962.6

300.5

897.0

332.0

135

DCC091TR-18GVWW

5

965.2

251.9

915.7

275.7

860.4

303.4

800.1

335.1

6

993.5

253.4

942.8

277.3

885.9

305.2

823.9

336.9

7

1022.2

255.0

970.2

279.0

911.8

306.9

848.1

338.7

8

1051.3

256.6

997.9

280.7

938.0

308.8

872.7

340.6

9

1080.6

258.1

1025.9

282.5

964.6

310.6

897.7

342.5

10

1110.3

259.8

1054.3

284.2

991.4

312.5

923.0

344.5

136

DCC094TR-18GWWW

5

995.9

261.6

944.5

286.0

886.9

314.4

824.0

346.6

6

1024.8

263.3

972.1

287.9

912.9

316.3

848.3

348.6

7

1054.2

265.0

1000.0

289.7

939.2

318.3

872.9

350.6

8

1083.8

266.8

1028.3

291.6

965.9

320.3

897.9

352.7

9

1113.7

268.5

1056.8

293.6

992.9

322.4

923.3

354.8

10

1143.9

270.3

1085.7

295.5

1020.3

324.4

949.0

356.9

137

DCC082TR-19GYYV

5

857.0

216.4

815.5

236.7

769.0

260.8

718.1

288.6

6

882.9

217.4

840.3

237.8

792.5

262.0

740.2

289.8

7

908.6

218.5

865.4

238.9

816.4

263.1

762.7

291.0

8

935.5

219.6

890.8

240.1

840.6

264.3

785.5

292.2

9

962.2

220.7

916.6

241.3

865.1

265.6

808.7

293.5

10

989.3

221.8

942.6

242.5

889.9

266.8

832.3

294.8

138

DCC084TR-20GYVV

5

882.6

223.3

840.3

244.3

792.8

269.1

740.6

297.9

6

909.0

224.3

865.8

245.4

817.0

270.3

763.4

299.1

7

935.7

225.3

891.5

246.4

841.5

271.4

786.6

300.3

8

963.0

226.4

917.6

247.6

866.4

272.6

810.1

301.5

9

990.4

227.4

944.0

248.7

891.6

273.8

834.0

302.8

10

1018.1

228.5

970.7

249.9

917.1

275.0

858.2

304.1

139

DCC087TR-21GVVV

5

908.1

230.2

865.1

251.8

816.6

277.5

763.2

307.2

6

935.2

231.2

891.2

252.9

841.4

278.6

786.6

308.4

7

962.7

232.2

917.7

254.0

866.7

279.7

810.4

309.6

8

990.5

233.2

944.4

255.0

892.2

280.9

834.6

310.8

9

1018.6

234.2

971.5

256.1

918.1

282.1

859.2

312.0

10

1046.9

235.2

998.9

257.3

944.3

283.3

884.1

313.3

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

DCC Performance Data AC Fans

Advertising