Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 178: Dcc performance data ac fans
![background image](/manuals/370937/178/background.png)
178
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
134
DCC088TR-18GVVW
5
934.4
242.2
887.0
265.3
833.9
292.5
776.2
323.6
6
962.2
243.6
913.5
266.8
859.0
294.0
799.6
325.2
7
990.3
244.9
940.3
268.3
884.4
295.6
823.4
326.8
8
1018.8
246.3
967.5
269.8
910.1
297.2
847.6
328.5
9
1047.6
247.8
995.0
271.4
936.2
298.9
872.1
330.2
10
1076.7
249.2
1022.8
272.9
962.6
300.5
897.0
332.0
135
DCC091TR-18GVWW
5
965.2
251.9
915.7
275.7
860.4
303.4
800.1
335.1
6
993.5
253.4
942.8
277.3
885.9
305.2
823.9
336.9
7
1022.2
255.0
970.2
279.0
911.8
306.9
848.1
338.7
8
1051.3
256.6
997.9
280.7
938.0
308.8
872.7
340.6
9
1080.6
258.1
1025.9
282.5
964.6
310.6
897.7
342.5
10
1110.3
259.8
1054.3
284.2
991.4
312.5
923.0
344.5
136
DCC094TR-18GWWW
5
995.9
261.6
944.5
286.0
886.9
314.4
824.0
346.6
6
1024.8
263.3
972.1
287.9
912.9
316.3
848.3
348.6
7
1054.2
265.0
1000.0
289.7
939.2
318.3
872.9
350.6
8
1083.8
266.8
1028.3
291.6
965.9
320.3
897.9
352.7
9
1113.7
268.5
1056.8
293.6
992.9
322.4
923.3
354.8
10
1143.9
270.3
1085.7
295.5
1020.3
324.4
949.0
356.9
137
DCC082TR-19GYYV
5
857.0
216.4
815.5
236.7
769.0
260.8
718.1
288.6
6
882.9
217.4
840.3
237.8
792.5
262.0
740.2
289.8
7
908.6
218.5
865.4
238.9
816.4
263.1
762.7
291.0
8
935.5
219.6
890.8
240.1
840.6
264.3
785.5
292.2
9
962.2
220.7
916.6
241.3
865.1
265.6
808.7
293.5
10
989.3
221.8
942.6
242.5
889.9
266.8
832.3
294.8
138
DCC084TR-20GYVV
5
882.6
223.3
840.3
244.3
792.8
269.1
740.6
297.9
6
909.0
224.3
865.8
245.4
817.0
270.3
763.4
299.1
7
935.7
225.3
891.5
246.4
841.5
271.4
786.6
300.3
8
963.0
226.4
917.6
247.6
866.4
272.6
810.1
301.5
9
990.4
227.4
944.0
248.7
891.6
273.8
834.0
302.8
10
1018.1
228.5
970.7
249.9
917.1
275.0
858.2
304.1
139
DCC087TR-21GVVV
5
908.1
230.2
865.1
251.8
816.6
277.5
763.2
307.2
6
935.2
231.2
891.2
252.9
841.4
278.6
786.6
308.4
7
962.7
232.2
917.7
254.0
866.7
279.7
810.4
309.6
8
990.5
233.2
944.4
255.0
892.2
280.9
834.6
310.8
9
1018.6
234.2
971.5
256.1
918.1
282.1
859.2
312.0
10
1046.9
235.2
998.9
257.3
944.3
283.3
884.1
313.3
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data AC Fans