Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 173: Dcc performance data ac fans
![background image](/manuals/370937/173/background.png)
173
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
104
DCC058DR-10DVW0
5
619.3
168.7
586.3
185.2
549.6
204.4
509.8
226.1
6
637.1
169.8
603.2
186.4
565.4
205.7
524.6
227.5
7
655.0
171.0
620.2
187.7
581.5
207.0
539.6
228.8
8
673.2
172.2
637.5
189.0
597.7
208.4
554.8
230.3
9
691.4
173.4
654.1
190.5
614.2
209.8
570.3
231.7
10
709.9
174.6
672.5
191.6
630.9
211.2
586.0
233.2
105
DCC061DR-10DWW0
5
656.0
179.6
619.9
196.8
579.9
216.6
536.6
238.8
6
674.6
181.0
637.5
198.3
596.3
218.1
552.0
240.4
7
693.4
182.4
655.3
199.8
613.0
219.7
567.5
242.0
8
712.4
183.8
673.2
201.3
629.9
221.3
583.2
243.6
9
731.5
185.2
691.4
202.8
647.0
222.9
599.2
245.2
10
750.8
186.7
709.7
204.4
664.2
224.6
615.4
246.9
106
DCC065TR-10GPPY
5
693.7
195.6
654.4
214.8
611.1
236.9
564.8
261.7
6
713.5
197.1
673.0
216.5
628.6
238.6
581.0
263.4
7
733.5
198.7
691.9
218.2
646.2
240.4
597.4
265.2
8
753.7
200.4
710.9
219.9
664.1
242.2
614.0
267.0
9
774.1
202.0
730.2
221.7
682.1
244.1
630.9
268.9
10
794.6
203.7
749.6
223.5
700.4
245.9
648.0
270.8
107
DCC050DR-12EPV0
5
527.7
133.9
502.8
146.3
474.5
160.8
443.3
177.7
6
543.2
134.6
517.8
147.0
488.8
161.6
456.7
178.4
7
558.9
135.2
532.9
147.6
503.2
162.3
470.4
179.2
8
574.8
135.8
548.2
148.3
517.8
163.0
484.2
180.0
9
590.7
136.5
563.6
149.0
532.6
163.8
498.2
180.7
10
606.7
137.1
579.2
149.8
547.6
164.6
512.4
181.6
108
DCC052DR-12EYY0
5
543.6
139.2
517.9
152.4
488.8
167.9
456.9
185.8
6
559.8
139.9
533.4
153.1
503.6
168.7
470.9
186.6
7
576.1
140.6
549.2
153.8
518.6
169.4
485.0
187.4
8
592.6
141.3
565.0
154.6
533.8
170.2
499.4
188.2
9
609.2
142.0
581.1
155.3
549.2
171.0
514.0
189.0
10
625.9
142.7
597.3
156.1
564.7
171.8
528.8
189.9
109
DCC054DR-11DYV0
5
572.5
148.3
544.0
162.7
511.5
179.8
477.2
199.2
6
589.4
149.1
560.1
163.6
527.3
180.6
491.5
200.1
7
606.4
149.9
576.4
164.5
542.8
181.5
506.1
201.1
8
623.6
150.8
592.9
165.4
558.5
182.5
520.9
202.1
9
641.0
151.6
609.6
166.3
574.4
183.5
535.9
203.1
10
658.6
152.5
626.5
167.2
590.4
184.5
551.2
204.1
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data AC Fans