Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 143: Dcf electrical data - regular quiet

Advertising
background image

143

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

40

41

42

Unit Data

DCF085TR-18GYYY

DCF088TR-17HYVV

DCF093TR-18HVVV

Nominal Run Amps

(1)

A

526.0

572.0

601.4

Maximum Start Amps

A

762.6

800.4

809.8

Recommended Mains Fuse Size

A

560

630

630

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

18

17

18

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

18

17

18

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

18

17

18

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5 / 47.5

47.5 / 55.2 / 55.2

55.2 / 55.2 / 55.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 29.6 / 29.6

29.6 / 33.1 / 33.1

33.1 / 33.1 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287 / 287

287 / 267 / 267

267 / 267 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

485.4

517.0

537.4

Reactive power reduction/saving

(4)

kVAr

70.3

91.2

104.0

Maximum Start Amps

A

722.0

745.4

745.8

Recommended Mains Fuse Size

A

560

630

630

Electronic Soft-start
Nominal Run Amps

A

526.0

572.0

601.4

Maximum Start Amps

A

647.8

685.6

703.0

Recommended Mains Fuse

A

560

630

630

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

485.4

517.0

537.4

Maximum Start Amps

A

607.2

630.6

639.0

Recommended Mains Fuse Size

A

560.0

630.0

630.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

554.5

600.5

629.9

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

16.4

16.4

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

35.0

Unit Nominal Run Amps

A

560.9

607.0

636.4

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

20.3

20.3

20.3

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

547.4

592.9

622.1

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

16.8

16.8

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

33.2

Unit Nominal Run Amps

A

552.4

597.8

627.0

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

20.7

20.7

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.