Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data - regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 142
![background image](/manuals/370937/142/background.png)
142
Chiller Technical Manual 7267818 V1.4.0_04_2014
Chillers
DeltaChill™ Air Cooled and FreeCool
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
37
38
39
Unit Data
DCF094TR-15HVWW
DCF096TR-15HWWW
DCF080TR-17GPYY
Nominal Run Amps
(1)
A
613.2
625.3
496.4
Maximum Start Amps
A
848.5
860.6
731.7
Recommended Mains Fuse Size
A
670
670
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
15
15
17
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
15
15
17
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
15
15
17
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
59.2 / 47.5 / 47.5
Quantity
3 + 3 + 3
3 + 3 + 3
2 + 3 + 3
Motor Rating
kW
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
36.2 / 29.6 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 298 / 298
298 / 298 / 298
298 / 287 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
556.5
570.7
455.5
Reactive power reduction/saving
(4)
kVAr
94.7
92.4
70.0
Maximum Start Amps
A
791.8
806.0
690.8
Recommended Mains Fuse Size
A
670
670
560
Electronic Soft-start
Nominal Run Amps
A
613.2
625.3
496.4
Maximum Start Amps
A
729.3
741.4
612.5
Recommended Mains Fuse
A
670
670
560
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
556.5
570.7
455.5
Maximum Start Amps
A
672.6
686.8
571.6
Recommended Mains Fuse Size
A
670.0
670.0
560.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
35.0
28.5
Unit Nominal Run Amps
A
641.6
660.3
524.9
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
16.4
20.3
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
41.5
35.0
Unit Nominal Run Amps
A
648.1
666.7
531.4
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
20.3
23.9
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
33.2
26.9
Unit Nominal Run Amps
A
634.2
651.4
517.7
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
16.8
20.7
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
39.2
33.2
Unit Nominal Run Amps
A
639.1
656.1
522.7
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
20.7
24.4
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet