Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data - regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 142

Advertising
background image

142

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

ELECTRICAL DATA

37

38

39

Unit Data

DCF094TR-15HVWW

DCF096TR-15HWWW

DCF080TR-17GPYY

Nominal Run Amps

(1)

A

613.2

625.3

496.4

Maximum Start Amps

A

848.5

860.6

731.7

Recommended Mains Fuse Size

A

670

670

560

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

15

15

17

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

15

15

17

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

15

15

17

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 59.2 / 59.2

59.2 / 59.2 / 59.2

59.2 / 47.5 / 47.5

Quantity

3 + 3 + 3

3 + 3 + 3

2 + 3 + 3

Motor Rating

kW

33.1 / 36.2 / 36.2

36.2 / 36.2 / 36.2

36.2 / 29.6 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 298 / 298

298 / 298 / 298

298 / 287 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

556.5

570.7

455.5

Reactive power reduction/saving

(4)

kVAr

94.7

92.4

70.0

Maximum Start Amps

A

791.8

806.0

690.8

Recommended Mains Fuse Size

A

670

670

560

Electronic Soft-start
Nominal Run Amps

A

613.2

625.3

496.4

Maximum Start Amps

A

729.3

741.4

612.5

Recommended Mains Fuse

A

670

670

560

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

556.5

570.7

455.5

Maximum Start Amps

A

672.6

686.8

571.6

Recommended Mains Fuse Size

A

670.0

670.0

560.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

35.0

28.5

Unit Nominal Run Amps

A

641.6

660.3

524.9

Recommended Mains Fuse Size

A

670

710

560

Motor Rating

kW

16.4

20.3

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

41.5

35.0

Unit Nominal Run Amps

A

648.1

666.7

531.4

Recommended Mains Fuse Size

A

670

710

560

Motor Rating

kW

20.3

23.9

20.3

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

26.9

33.2

26.9

Unit Nominal Run Amps

A

634.2

651.4

517.7

Recommended Mains Fuse Size

A

670

710

560

Motor Rating

kW

16.8

20.7

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

39.2

33.2

Unit Nominal Run Amps

A

639.1

656.1

522.7

Recommended Mains Fuse Size

A

670

710

560

Motor Rating

kW

20.7

24.4

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet

Advertising
This manual is related to the following products: