Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 254: Dcc electrical data - extra quiet

Advertising
background image

254

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

ELECTRICAL DATA

170

171

172

Unit Data

DCC086TX-18GVVW

DCC088TX-18GVWW

DCC091TX-18GWWW

Nominal Run Amps

(1)

A

583.4

595.6

607.9

Maximum Start Amps

A

818.7

830.9

843.2

Recommended Mains Fuse Size

A

630

630

630

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

18

18

18

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

18

18

18

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 55.2 / 59.2

55.2 / 59.2 / 59.2

59.2 / 59.2 / 59.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

33.1 / 33.1 / 36.2

33.1 / 36.2 / 36.2

36.2 / 36.2 / 36.2

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 267 / 298

267 / 298 / 298

298 / 298 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

531.6

545.7

559.8

Reactive power reduction/saving

(4)

kVAr

87.5

85.2

82.9

Maximum Start Amps

A

766.9

781.0

795.1

Recommended Mains Fuse Size

A

630

630

630

Electronic Soft-start
Nominal Run Amps

A

583.4

595.6

607.9

Maximum Start Amps

A

699.5

711.7

724.0

Recommended Mains Fuse

A

630

630

630

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

531.6

545.7

559.8

Maximum Start Amps

A

647.7

661.8

675.9

Recommended Mains Fuse Size

A

630

630

630

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

15.2

Unit Nominal Run Amps

A

594.6

606.7

622.9

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

6.2

6.2

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

604.6

616.8

629.0

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

13.9

Unit Nominal Run Amps

A

591.4

603.7

618.8

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

6.4

6.4

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

599.0

611.2

623.6

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

12.4

12.4

12.4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Extra Quiet