Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 243: Dcc electrical data - regular quiet

Advertising
background image

243

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

137

138

139

Unit Data

DCC082TR-19GYYV

DCC084TR-20GYVV

DCC087TR-21GVVV

Nominal Run Amps

(1)

A

555.1

584.3

613.8

Maximum Start Amps

A

783.5

812.7

822.2

Recommended Mains Fuse Size

A

630

630

670

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

19

20

21

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

19

20

21

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5 / 55.2

47.5 / 55.2 / 55.2

55.2 / 55.2 / 55.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 29.6 / 33.1

29.6 / 33.1 / 33.1

33.1 / 33.1 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287 / 267

287 / 267 / 267

267 / 267 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

505.8

526.1

546.5

Reactive power reduction/saving

(4)

kVAr

83.1

95.9

108.6

Maximum Start Amps

A

734.2

754.5

754.9

Recommended Mains Fuse Size

A

630

630

670

Electronic Soft-start
Nominal Run Amps

A

555.1

584.3

613.8

Maximum Start Amps

A

668.7

697.9

715.4

Recommended Mains Fuse

A

630

630

670

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

505.8

526.1

546.5

Maximum Start Amps

A

619.4

639.7

648.1

Recommended Mains Fuse Size

A

630

630

670

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

566.2

595.5

625.0

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

6.2

6.2

6.2

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

576.2

605.5

635.0

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

10.2

Unit Nominal Run Amps

A

563.0

592.2

621.6

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

6.4

6.4

6.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

570.6

599.7

629.0

Recommended Mains Fuse Size

A

630

630

670

Motor Rating

kW

12.4

12.4

12.4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Regular Quiet