ELECTRICAL DATA
67
68
69
Unit Data
DCF057DX-13DYV0
DCF057DX-14DYY0
DCF060DX-14DVV0
Nominal Run Amps
(1)
A
358.3
336.0
385.8
Maximum Start Amps
A
586.7
572.6
594.2
Recommended Mains Fuse Size
A
400
355
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
13
14
14
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
13
14
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 55.2
47.5 / 47.5
55.2 / 55.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
29.6 / 33.1
29.6 / 29.6
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 267
287 / 287
267 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
329.6
314.2
348.8
Reactive power reduction/saving
(4)
kVAr
49.4
38.9
61.4
Maximum Start Amps
A
558.0
550.8
557.2
Recommended Mains Fuse Size
A
400
355
450
Electronic Soft-start
Nominal Run Amps
A
358.3
336.0
385.8
Maximum Start Amps
A
471.9
457.8
487.4
Recommended Mains Fuse
A
400
355
450
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
329.6
314.2
348.8
Maximum Start Amps
A
443.2
436.0
450.4
Recommended Mains Fuse Size
A
400
355
450
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
21.2
Unit Nominal Run Amps
A
373.0
350.6
406.9
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
8.4
8.4
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
28.5
Unit Nominal Run Amps
A
379.4
357.0
414.2
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
12.1
12.1
16.4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
19.8
Unit Nominal Run Amps
A
369.2
347.1
401.2
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
8.6
8.6
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
26.9
Unit Nominal Run Amps
A
374.0
351.9
406.8
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
12.4
12.4
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet