ELECTRICAL DATA

67

68

69

Unit Data

DCF057DX-13DYV0

DCF057DX-14DYY0

DCF060DX-14DVV0

Nominal Run Amps

(1)

A

358.3

336.0

385.8

Maximum Start Amps

A

586.7

572.6

594.2

Recommended Mains Fuse Size

A

400

355

450

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

13

14

14

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

13

14

14

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 55.2

47.5 / 47.5

55.2 / 55.2

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

29.6 / 33.1

29.6 / 29.6

33.1 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 267

287 / 287

267 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

329.6

314.2

348.8

Reactive power reduction/saving

(4)

kVAr

49.4

38.9

61.4

Maximum Start Amps

A

558.0

550.8

557.2

Recommended Mains Fuse Size

A

400

355

450

Electronic Soft-start
Nominal Run Amps

A

358.3

336.0

385.8

Maximum Start Amps

A

471.9

457.8

487.4

Recommended Mains Fuse

A

400

355

450

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

329.6

314.2

348.8

Maximum Start Amps

A

443.2

436.0

450.4

Recommended Mains Fuse Size

A

400

355

450

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

14.8

21.2

Unit Nominal Run Amps

A

373.0

350.6

406.9

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

8.4

8.4

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

28.5

Unit Nominal Run Amps

A

379.4

357.0

414.2

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

12.1

12.1

16.4

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

19.8

Unit Nominal Run Amps

A

369.2

347.1

401.2

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

8.6

8.6

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

26.9

Unit Nominal Run Amps

A

374.0

351.9

406.8

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

12.4

12.4

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet