ELECTRICAL DATA
82
83
84
Unit Data
DCF082TX-18GYYY
DCF085TX-17HYVV
DCF089TX-18HVVV
Nominal Run Amps
(1)
A
496.7
543.8
571.3
Maximum Start Amps
A
733.3
772.2
779.7
Recommended Mains Fuse Size
A
560
560
630
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
18
17
18
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
18
17
18
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5 / 47.5
47.5 / 55.2 / 55.2
55.2 / 55.2 / 55.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
29.6 / 29.6 / 29.6
29.6 / 33.1 / 33.1
33.1 / 33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287 / 287
287 / 267 / 267
267 / 267 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
465.5
498.2
517.4
Reactive power reduction/saving
(4)
kVAr
56.1
77.8
89.8
Maximum Start Amps
A
702.1
726.6
725.8
Recommended Mains Fuse Size
A
560
560
630
Electronic Soft-start
Nominal Run Amps
A
496.7
543.8
571.3
Maximum Start Amps
A
618.5
657.4
672.9
Recommended Mains Fuse
A
560
560
630
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
465.5
498.2
517.4
Maximum Start Amps
A
587.3
611.8
619.0
Recommended Mains Fuse Size
A
560
560
630
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
525.1
572.2
599.8
Recommended Mains Fuse Size
A
560
630
630
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
531.6
578.7
606.3
Recommended Mains Fuse Size
A
560
630
630
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
518.4
565.0
592.3
Recommended Mains Fuse Size
A
560
630
630
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
523.5
570.0
597.2
Recommended Mains Fuse Size
A
560
630
630
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.