Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 157: Dcf electrical data extra quiet

Advertising
background image

157

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

82

83

84

Unit Data

DCF082TX-18GYYY

DCF085TX-17HYVV

DCF089TX-18HVVV

Nominal Run Amps

(1)

A

496.7

543.8

571.3

Maximum Start Amps

A

733.3

772.2

779.7

Recommended Mains Fuse Size

A

560

560

630

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

18

17

18

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

18

17

18

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5 / 47.5

47.5 / 55.2 / 55.2

55.2 / 55.2 / 55.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 29.6 / 29.6

29.6 / 33.1 / 33.1

33.1 / 33.1 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287 / 287

287 / 267 / 267

267 / 267 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

465.5

498.2

517.4

Reactive power reduction/saving

(4)

kVAr

56.1

77.8

89.8

Maximum Start Amps

A

702.1

726.6

725.8

Recommended Mains Fuse Size

A

560

560

630

Electronic Soft-start
Nominal Run Amps

A

496.7

543.8

571.3

Maximum Start Amps

A

618.5

657.4

672.9

Recommended Mains Fuse

A

560

560

630

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

465.5

498.2

517.4

Maximum Start Amps

A

587.3

611.8

619.0

Recommended Mains Fuse Size

A

560

560

630

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

525.1

572.2

599.8

Recommended Mains Fuse Size

A

560

630

630

Motor Rating

kW

16.4

16.4

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

35.0

Unit Nominal Run Amps

A

531.6

578.7

606.3

Recommended Mains Fuse Size

A

560

630

630

Motor Rating

kW

20.3

20.3

20.3

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

518.4

565.0

592.3

Recommended Mains Fuse Size

A

560

630

630

Motor Rating

kW

16.8

16.8

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

33.2

Unit Nominal Run Amps

A

523.5

570.0

597.2

Recommended Mains Fuse Size

A

560

630

630

Motor Rating

kW

20.7

20.7

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet

Advertising
This manual is related to the following products: