ELECTRICAL DATA

73

74

75

Unit Data

DCF075TX-14GPYY

DCF059DX-15DYV0

DCF061DX-16DVV0

Nominal Run Amps

(1)

A

461.4

363.1

390.6

Maximum Start Amps

A

696.7

591.5

599.0

Recommended Mains Fuse Size

A

500

400

450

Evaporator
Immersion Heater Rating

W

250

170

170

Condenser Fan - Per Fan (AC)
Quantity

14

15

16

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

14

15

16

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 47.5 / 47.5

47.5 / 55.2

55.2 / 55.2

Quantity

2 + 3 + 3

3 + 3

3 + 3

Motor Rating

kW

36.2 / 29.6 / 29.6

29.6 / 33.1

33.1 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 287 / 287

287 / 267

267 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

430.9

333.4

352.7

Reactive power reduction/saving

(4)

kVAr

54.3

50.9

62.9

Maximum Start Amps

A

666.2

561.8

561.1

Recommended Mains Fuse Size

A

500

400

450

Electronic Soft-start
Nominal Run Amps

A

461.4

363.1

390.6

Maximum Start Amps

A

577.5

476.7

492.2

Recommended Mains Fuse

A

500

400

450

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

430.9

333.4

352.7

Maximum Start Amps

A

547.0

447.0

454.3

Recommended Mains Fuse Size

A

500

400

450

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

482.4

384.3

411.8

Recommended Mains Fuse Size

A

500

450

450

Motor Rating

kW

12.1

12.1

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

489.7

391.6

419.1

Recommended Mains Fuse Size

A

560

450

450

Motor Rating

kW

16.4

16.4

16.4

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

477.3

378.8

406.1

Recommended Mains Fuse Size

A

500

400

450

Motor Rating

kW

12.4

12.4

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

483.0

384.4

411.6

Recommended Mains Fuse Size

A

560

450

450

Motor Rating

kW

16.8

16.8

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet