ELECTRICAL DATA
73
74
75
Unit Data
DCF075TX-14GPYY
DCF059DX-15DYV0
DCF061DX-16DVV0
Nominal Run Amps
(1)
A
461.4
363.1
390.6
Maximum Start Amps
A
696.7
591.5
599.0
Recommended Mains Fuse Size
A
500
400
450
Evaporator
Immersion Heater Rating
W
250
170
170
Condenser Fan - Per Fan (AC)
Quantity
14
15
16
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
14
15
16
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 47.5 / 47.5
47.5 / 55.2
55.2 / 55.2
Quantity
2 + 3 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 29.6 / 29.6
29.6 / 33.1
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 287 / 287
287 / 267
267 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
430.9
333.4
352.7
Reactive power reduction/saving
(4)
kVAr
54.3
50.9
62.9
Maximum Start Amps
A
666.2
561.8
561.1
Recommended Mains Fuse Size
A
500
400
450
Electronic Soft-start
Nominal Run Amps
A
461.4
363.1
390.6
Maximum Start Amps
A
577.5
476.7
492.2
Recommended Mains Fuse
A
500
400
450
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
430.9
333.4
352.7
Maximum Start Amps
A
547.0
447.0
454.3
Recommended Mains Fuse Size
A
500
400
450
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
482.4
384.3
411.8
Recommended Mains Fuse Size
A
500
450
450
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
489.7
391.6
419.1
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
477.3
378.8
406.1
Recommended Mains Fuse Size
A
500
400
450
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
483.0
384.4
411.6
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet