Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

1

Output kW refers to the chilled water duty (Based upon 20% Ethylene Glycol).

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

43 DCF095TR-18HVVW

6

956.3

248.6

907.1

272.7

852.5

300.6

793.2

332.4

7

983.8

250.1

933.3

274.3

877.3

302.3

816.4

334.2

8

1011.6

251.6

959.8

275.9

902.4

304.0

840.0

336.0

10

1068.1

254.8

1013.8

279.3

953.5

307.6

888.1

339.7

12

1125.7

258.0

1068.9

282.8

1005.9

311.3

937.6

343.6

14

1184.1

261.3

1125.0

286.4

1059.4

315.2

988.3

347.7

44 DCF098TR-18HVWW

6

986.5

258.8

935.3

283.5

878.4

312.0

816.5

344.4

7

1014.5

260.4

962.0

285.3

903.6

313.9

840.0

346.3

8

1042.9

262.1

989.0

287.1

929.1

315.8

863.9

348.3

10

1100.4

265.6

1043.9

290.9

981.1

319.8

912.8

352.5

12

1158.9

269.1

1099.9

294.8

1034.2

324.0

962.9

356.8

14

1218.1

272.8

1156.8

298.8

1088.4

328.3

1014.3

361.3

45 DCF100TR-18HWWW

6

1008.3

268.3

955.7

293.7

897.1

322.8

833.3

355.7

7

1036.8

270.2

982.8

295.7

922.6

324.9

857.1

357.9

8

1065.6

272.0

1010.2

297.7

948.5

327.1

881.2

360.1

10

1123.9

275.8

1065.9

301.8

1001.1

331.4

930.6

364.6

12

1183.2

279.7

1122.6

306.1

1054.8

336.0

981.2

369.3

14

1243.1

283.7

1180.1

310.5

1109.7

340.7

1033.1

374.2

46 DCF088TR-19HYYV

6

871.5

221.3

829.0

242.4

781.7

267.0

730.1

295.3

7

897.0

222.4

853.5

243.6

805.0

268.3

752.0

296.6

8

922.8

223.6

878.3

244.8

828.6

269.6

774.3

298.0

10

975.3

226.0

928.7

247.3

876.6

272.3

819.8

300.7

12

1028.8

228.5

980.3

250.0

925.9

275.0

866.5

303.6

14

1083.1

231.1

1032.7

252.7

976.2

277.9

914.5

306.7

47 DCF090TR-20HYVV

6

897.0

228.3

853.8

250.0

805.6

275.5

752.8

304.7

7

923.1

229.4

878.9

251.2

829.5

276.7

775.4

306.0

8

949.6

230.5

904.4

252.4

853.8

278.0

798.3

307.4

10

1003.4

232.8

956.2

254.8

903.2

280.6

845.1

310.1

12

1058.1

235.2

1009.0

257.4

953.8

283.3

893.2

313.0

14

1113.4

237.6

1062.6

260.1

1005.4

286.2

942.5

316.0

48 DCF095TR-21HVVV

6

942.0

236.0

895.9

258.4

844.6

284.6

788.7

314.9

7

969.7

237.1

922.4

259.6

869.9

285.9

812.5

316.2

8

997.7

238.2

949.3

260.8

895.5

287.2

836.6

317.6

10

1054.9

240.5

1004.2

263.3

947.7

289.8

886.0

320.4

12

1113.3

242.9

1060.4

265.9

1001.3

292.6

936.9

323.3

14

1172.8

245.5

1117.7

268.6

1056.1

295.5

989.0

326.4

49 DCF098TR-21HVVW

6

973.3

245.6

925.4

268.6

872.0

295.5

813.1

326.4

7

1001.6

246.8

952.5

270.0

897.7

297.0

837.7

327.9

8

1030.3

248.1

980.0

271.4

923.8

298.4

862.3

329.4

10

1088.6

250.7

1035.9

274.2

977.0

301.5

912.6

332.6

12

1148.0

253.5

1093.1

277.2

1031.5

304.6

964.2

335.9

14

1208.2

256.2

1151.2

280.2

1087.2

307.9

1017.2

339.4