Page 250: Dcc electrical data - extra quiet
250
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
ELECTRICAL DATA
158
159
160
Unit Data
DCC070TX-14GPYY
DCC055DX-15DYV0
DCC059DX-16DVV0
Nominal Run Amps
(1)
A
461.4
363.1
390.6
Maximum Start Amps
A
696.7
591.5
599.0
Recommended Mains Fuse Size
A
500
400
450
Evaporator
Immersion Heater Rating
W
250
170
170
Condenser Fan - Per Fan (AC)
Quantity
14
15
16
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
14
15
16
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 47.5 / 47.5
47.5 / 55.2
55.2 / 55.2
Quantity
2 + 3 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 29.6 / 29.6
29.6 / 33.1
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 287 / 287
287 / 267
267 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
430.9
333.4
352.7
Reactive power reduction/saving
(4)
kVAr
54.3
50.9
62.9
Maximum Start Amps
A
666.2
561.8
561.1
Recommended Mains Fuse Size
A
500
400
450
Electronic Soft-start
Nominal Run Amps
A
461.4
363.1
390.6
Maximum Start Amps
A
577.5
476.7
492.2
Recommended Mains Fuse
A
500
400
450
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
430.9
333.4
352.7
Maximum Start Amps
A
547.0
447.0
454.3
Recommended Mains Fuse Size
A
500
400
450
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
8.9
11.2
Unit Nominal Run Amps
A
472.4
371.7
401.8
Recommended Mains Fuse Size
A
500
400
450
Motor Rating
kW
6.2
4.4
6.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
11.2
11.2
Unit Nominal Run Amps
A
482.4
374.2
401.8
Recommended Mains Fuse Size
A
500
400
450
Motor Rating
kW
12.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
7.3
10.2
Unit Nominal Run Amps
A
469.6
368.8
398.6
Recommended Mains Fuse Size
A
500
400
450
Motor Rating
kW
6.4
4.5
6.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
10.1
10.1
Unit Nominal Run Amps
A
477.3
371.1
398.5
Recommended Mains Fuse Size
A
500
400
450
Motor Rating
kW
12.4
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet