Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 234: Dcc electrical data - regular quiet

Advertising
background image

234

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

110

111

112

Unit Data

DCC058DR-12DVV0

DCC060DR-12DVW0

DCC063DR-12DWW0

Nominal Run Amps

(1)

A

400.9

413.0

425.1

Maximum Start Amps

A

609.3

648.3

660.4

Recommended Mains Fuse Size

A

450

450

450

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

12

12

12

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

12

12

12

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 55.2

55.2 / 59.2

59.2 / 59.2

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

33.1 / 33.1

33.1 / 36.2

36.2 / 36.2

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 267

267 / 298

298 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

358.3

372.4

386.5

Reactive power reduction/saving

(4)

kVAr

69.3

67.0

64.7

Maximum Start Amps

A

566.7

607.7

621.8

Recommended Mains Fuse Size

A

450

450

450

Electronic Soft-start
Nominal Run Amps

A

400.9

413.0

425.1

Maximum Start Amps

A

502.5

529.1

541.2

Recommended Mains Fuse

A

450

450

450

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

358.3

372.4

386.5

Maximum Start Amps

A

459.9

488.5

502.6

Recommended Mains Fuse Size

A

450

450

450

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

8.9

11.2

11.2

Unit Nominal Run Amps

A

409.6

424.1

436.2

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

4.4

6.2

6.2

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

14.8

14.8

Unit Nominal Run Amps

A

412.1

427.7

439.8

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

6.1

8.4

8.4

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

7.3

10.2

10.2

Unit Nominal Run Amps

A

406.5

420.9

433.0

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

4.5

6.4

6.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

10.1

13.9

13.9

Unit Nominal Run Amps

A

408.7

423.7

435.9

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

6.3

8.6

8.6

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Regular Quiet