Introduction

Chiller Technical Manual 7267818 V1.4.0_04_2014

DeltaChill™ Air Cooled and FreeCool

Electrical

Electrical Overview

A weatherproof electrical power and controls panel shall be situated at the end of the unit and contains:

Individual mains power isolation for each circuits compressors

Separate electrical isolation for fans

Dedicated bus-bar chamber for connection of incoming 3 phase and earth mains power supply

Emergency stop fitted to controls compartment door

Separate, fully accessible controls compartment allowing adjustment of set points whilst the unit is operational

Circuit breakers for protection of all major unit components

Phase rotation relay incorporating phase loss protection

The electrical power and control panel is wired to the latest European standards and codes of practice

Mains supply is 3 phase and a neutral is not required, refer to interconnecting wiring.

Separate 230V 1ph 50Hz permanent supply is required for the controls and safety features. Isolator allows for a

maximum cable size of 10 mm

Electrical terminals for external evaporator pipe work trace heating (230V / 500 Watt) are provided. The external

trace heating is fitted by others

Pumps

Circuit 3

Compressors

Bus-bar Chamber

Fans

Power Factor

Correction

Circuit 1

Compressors

Panel Ventilation

Controls

Circuit 2

Compressors

Location of Electrical components within the chiller.