Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 137: Dcf electrical data - regular quiet

Advertising
background image

137

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

22

23

24

Unit Data

DCF074TR-11GPYY

DCF079TR-12GYYY

DCF059DR-13DYV0

Nominal Run Amps

(1)

A

472.0

501.7

379.8

Maximum Start Amps

A

707.3

738.3

608.2

Recommended Mains Fuse Size

A

500

560

400

Evaporator
Immersion Heater Rating

W

250

250

170

Condenser Fan - Per Fan (AC)
Quantity

11

12

13

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

11

12

13

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

11

12

13

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 47.5 / 47.5

47.5 / 47.5 / 47.5

47.5 / 55.2

Quantity

2 + 3 + 3

3 + 3 + 3

3 + 3

Motor Rating

kW

36.2 / 29.6 / 29.6

29.6 / 29.6 / 29.6

29.6 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 287 / 287

287 / 287 / 287

287 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

437.3

467.2

344.0

Reactive power reduction/saving

(4)

kVAr

60.7

61.0

59.7

Maximum Start Amps

A

672.6

703.8

572.4

Recommended Mains Fuse Size

A

500

560

400

Electronic Soft-start
Nominal Run Amps

A

472.0

501.7

379.8

Maximum Start Amps

A

588.1

623.5

493.4

Recommended Mains Fuse

A

500

560

400

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

437.3

467.2

344.0

Maximum Start Amps

A

553.4

589.0

457.6

Recommended Mains Fuse Size

A

500.0

560.0

400.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

21.2

Unit Nominal Run Amps

A

500.4

530.1

400.9

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

16.4

16.4

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

28.5

Unit Nominal Run Amps

A

506.9

536.6

408.2

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

20.3

20.3

16.4

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

19.8

Unit Nominal Run Amps

A

493.5

523.3

395.3

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

16.8

16.8

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

26.9

Unit Nominal Run Amps

A

498.5

528.3

400.8

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

20.7

20.7

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet

Advertising
This manual is related to the following products: