Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 137: Dcf electrical data - regular quiet
![background image](/manuals/370937/137/background.png)
137
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
22
23
24
Unit Data
DCF074TR-11GPYY
DCF079TR-12GYYY
DCF059DR-13DYV0
Nominal Run Amps
(1)
A
472.0
501.7
379.8
Maximum Start Amps
A
707.3
738.3
608.2
Recommended Mains Fuse Size
A
500
560
400
Evaporator
Immersion Heater Rating
W
250
250
170
Condenser Fan - Per Fan (AC)
Quantity
11
12
13
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
11
12
13
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
11
12
13
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 47.5 / 47.5
47.5 / 47.5 / 47.5
47.5 / 55.2
Quantity
2 + 3 + 3
3 + 3 + 3
3 + 3
Motor Rating
kW
36.2 / 29.6 / 29.6
29.6 / 29.6 / 29.6
29.6 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 287 / 287
287 / 287 / 287
287 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
437.3
467.2
344.0
Reactive power reduction/saving
(4)
kVAr
60.7
61.0
59.7
Maximum Start Amps
A
672.6
703.8
572.4
Recommended Mains Fuse Size
A
500
560
400
Electronic Soft-start
Nominal Run Amps
A
472.0
501.7
379.8
Maximum Start Amps
A
588.1
623.5
493.4
Recommended Mains Fuse
A
500
560
400
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
437.3
467.2
344.0
Maximum Start Amps
A
553.4
589.0
457.6
Recommended Mains Fuse Size
A
500.0
560.0
400.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
21.2
Unit Nominal Run Amps
A
500.4
530.1
400.9
Recommended Mains Fuse Size
A
560
560
450
Motor Rating
kW
16.4
16.4
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
28.5
Unit Nominal Run Amps
A
506.9
536.6
408.2
Recommended Mains Fuse Size
A
560
560
450
Motor Rating
kW
20.3
20.3
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
19.8
Unit Nominal Run Amps
A
493.5
523.3
395.3
Recommended Mains Fuse Size
A
560
560
450
Motor Rating
kW
16.8
16.8
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
26.9
Unit Nominal Run Amps
A
498.5
528.3
400.8
Recommended Mains Fuse Size
A
560
560
450
Motor Rating
kW
20.7
20.7
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet