ELECTRICAL DATA
31
32
33
Unit Data
DCF085TR-14HYVV
DCF075TR-16GPPY
DCF082TR-15GYYY
Nominal Run Amps
(1)
A
559.7
466.9
513.9
Maximum Start Amps
A
788.1
702.2
750.5
Recommended Mains Fuse Size
A
630
500
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
14
16
15
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
14
16
15
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
14
16
15
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 55.2 / 55.2
59.2 / 59.2 / 47.5
47.5 / 47.5 / 47.5
Quantity
3 + 3 + 3
2 + 2 + 3
3 + 3 + 3
Motor Rating
kW
29.6 / 33.1 / 33.1
36.2 / 36.2 / 29.6
29.6 / 29.6 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 267 / 267
298 / 298 / 287
287 / 287 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
507.9
425.6
476.3
Reactive power reduction/saving
(4)
kVAr
86.6
69.7
65.7
Maximum Start Amps
A
736.3
660.9
712.9
Recommended Mains Fuse Size
A
630
500
560
Electronic Soft-start
Nominal Run Amps
A
559.7
466.9
513.9
Maximum Start Amps
A
673.3
583.0
635.7
Recommended Mains Fuse
A
630
500
560
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
507.9
425.6
476.3
Maximum Start Amps
A
621.5
541.7
598.1
Recommended Mains Fuse Size
A
630.0
500.0
560.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
21.2
28.5
Unit Nominal Run Amps
A
588.1
488.0
542.3
Recommended Mains Fuse Size
A
630
560
560
Motor Rating
kW
16.4
12.1
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
28.5
35.0
Unit Nominal Run Amps
A
594.6
495.3
548.8
Recommended Mains Fuse Size
A
630
560
630
Motor Rating
kW
20.3
16.4
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
19.8
26.9
Unit Nominal Run Amps
A
580.7
482.4
535.3
Recommended Mains Fuse Size
A
630
560
560
Motor Rating
kW
16.8
12.4
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
26.9
33.2
Unit Nominal Run Amps
A
585.6
488.0
540.4
Recommended Mains Fuse Size
A
630
560
630
Motor Rating
kW
20.7
16.8
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.