Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data - regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 140

Advertising
background image

140

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

ELECTRICAL DATA

31

32

33

Unit Data

DCF085TR-14HYVV

DCF075TR-16GPPY

DCF082TR-15GYYY

Nominal Run Amps

(1)

A

559.7

466.9

513.9

Maximum Start Amps

A

788.1

702.2

750.5

Recommended Mains Fuse Size

A

630

500

560

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

14

16

15

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

14

16

15

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

14

16

15

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 55.2 / 55.2

59.2 / 59.2 / 47.5

47.5 / 47.5 / 47.5

Quantity

3 + 3 + 3

2 + 2 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 33.1 / 33.1

36.2 / 36.2 / 29.6

29.6 / 29.6 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 267 / 267

298 / 298 / 287

287 / 287 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

507.9

425.6

476.3

Reactive power reduction/saving

(4)

kVAr

86.6

69.7

65.7

Maximum Start Amps

A

736.3

660.9

712.9

Recommended Mains Fuse Size

A

630

500

560

Electronic Soft-start
Nominal Run Amps

A

559.7

466.9

513.9

Maximum Start Amps

A

673.3

583.0

635.7

Recommended Mains Fuse

A

630

500

560

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

507.9

425.6

476.3

Maximum Start Amps

A

621.5

541.7

598.1

Recommended Mains Fuse Size

A

630.0

500.0

560.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

21.2

28.5

Unit Nominal Run Amps

A

588.1

488.0

542.3

Recommended Mains Fuse Size

A

630

560

560

Motor Rating

kW

16.4

12.1

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

28.5

35.0

Unit Nominal Run Amps

A

594.6

495.3

548.8

Recommended Mains Fuse Size

A

630

560

630

Motor Rating

kW

20.3

16.4

20.3

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

26.9

19.8

26.9

Unit Nominal Run Amps

A

580.7

482.4

535.3

Recommended Mains Fuse Size

A

630

560

560

Motor Rating

kW

16.8

12.4

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

26.9

33.2

Unit Nominal Run Amps

A

585.6

488.0

540.4

Recommended Mains Fuse Size

A

630

560

630

Motor Rating

kW

20.7

16.8

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet