Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 232: Dcc electrical data - regular quiet

Advertising
background image

232

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

104

105

106

Unit Data

DCC058DR-10DVW0

DCC061DR-10DWW0

DCC065TR-10GPPY

Nominal Run Amps

(1)

A

404.7

416.9

442.4

Maximum Start Amps

A

640.0

652.2

677.7

Recommended Mains Fuse Size

A

450

450

500

Evaporator
Immersion Heater Rating

W

170

170

250

Condenser Fan - Per Fan (AC)
Quantity

10

10

10

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

10

10

10

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 59.2

59.2 / 59.2

59.2 / 59.2 / 47.5

Quantity

3 + 3

3 + 3

2 + 2 + 3

Motor Rating

kW

33.1 / 36.2

36.2 / 36.2

36.2 / 36.2 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 298

298 / 298

298 / 298 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

366.3

380.4

407.3

Reactive power reduction/saving

(4)

kVAr

63.9

61.6

60.4

Maximum Start Amps

A

601.6

615.7

642.6

Recommended Mains Fuse Size

A

450

450

500

Electronic Soft-start
Nominal Run Amps

A

404.7

416.9

442.4

Maximum Start Amps

A

520.8

533.0

558.5

Recommended Mains Fuse

A

450

450

500

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

366.3

380.4

407.3

Maximum Start Amps

A

482.4

496.5

523.4

Recommended Mains Fuse Size

A

450

450

500

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

8.9

11.2

11.2

Unit Nominal Run Amps

A

413.4

428.0

453.5

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

4.4

6.2

6.2

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

14.8

14.8

Unit Nominal Run Amps

A

415.8

431.6

457.1

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

6.1

8.4

8.4

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

7.3

10.2

10.2

Unit Nominal Run Amps

A

410.4

424.9

450.4

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

4.5

6.4

6.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

10.1

13.9

13.9

Unit Nominal Run Amps

A

412.6

427.7

453.3

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

6.3

8.6

8.6

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Regular Quiet