Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 232: Dcc electrical data - regular quiet
232
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
104
105
106
Unit Data
DCC058DR-10DVW0
DCC061DR-10DWW0
DCC065TR-10GPPY
Nominal Run Amps
(1)
A
404.7
416.9
442.4
Maximum Start Amps
A
640.0
652.2
677.7
Recommended Mains Fuse Size
A
450
450
500
Evaporator
Immersion Heater Rating
W
170
170
250
Condenser Fan - Per Fan (AC)
Quantity
10
10
10
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
10
10
10
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2
59.2 / 59.2
59.2 / 59.2 / 47.5
Quantity
3 + 3
3 + 3
2 + 2 + 3
Motor Rating
kW
33.1 / 36.2
36.2 / 36.2
36.2 / 36.2 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 298
298 / 298
298 / 298 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
366.3
380.4
407.3
Reactive power reduction/saving
(4)
kVAr
63.9
61.6
60.4
Maximum Start Amps
A
601.6
615.7
642.6
Recommended Mains Fuse Size
A
450
450
500
Electronic Soft-start
Nominal Run Amps
A
404.7
416.9
442.4
Maximum Start Amps
A
520.8
533.0
558.5
Recommended Mains Fuse
A
450
450
500
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
366.3
380.4
407.3
Maximum Start Amps
A
482.4
496.5
523.4
Recommended Mains Fuse Size
A
450
450
500
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
11.2
11.2
Unit Nominal Run Amps
A
413.4
428.0
453.5
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
4.4
6.2
6.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
14.8
14.8
Unit Nominal Run Amps
A
415.8
431.6
457.1
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
6.1
8.4
8.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
7.3
10.2
10.2
Unit Nominal Run Amps
A
410.4
424.9
450.4
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
4.5
6.4
6.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
10.1
13.9
13.9
Unit Nominal Run Amps
A
412.6
427.7
453.3
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
6.3
8.6
8.6
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet