Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 139: Dcf electrical data - regular quiet
139
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
28
29
30
Unit Data
DCF073TR-13GPPY
DCF078TR-14GPYY
DCF082TR-13HYYV
Nominal Run Amps
(1)
A
454.6
484.2
530.6
Maximum Start Amps
A
689.9
719.5
759.0
Recommended Mains Fuse Size
A
500
560
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
13
14
13
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
13
14
13
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
13
14
13
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 59.2 / 47.5
59.2 / 47.5 / 47.5
47.5 / 47.5 / 55.2
Quantity
2 + 2 + 3
2 + 3 + 3
3 + 3 + 3
Motor Rating
kW
36.2 / 36.2 / 29.6
36.2 / 29.6 / 29.6
29.6 / 29.6 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 298 / 287
298 / 287 / 287
287 / 287 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
416.5
446.4
487.6
Reactive power reduction/saving
(4)
kVAr
65.1
65.4
73.8
Maximum Start Amps
A
651.8
681.7
716.0
Recommended Mains Fuse Size
A
500
560
560
Electronic Soft-start
Nominal Run Amps
A
454.6
484.2
530.6
Maximum Start Amps
A
570.7
600.3
644.2
Recommended Mains Fuse
A
500
560
560
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
416.5
446.4
487.6
Maximum Start Amps
A
532.6
562.5
601.2
Recommended Mains Fuse Size
A
500.0
560.0
560.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
28.5
28.5
Unit Nominal Run Amps
A
475.7
512.6
559.0
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
12.1
16.4
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
35.0
35.0
Unit Nominal Run Amps
A
483.0
519.1
565.5
Recommended Mains Fuse Size
A
560
560
630
Motor Rating
kW
16.4
20.3
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
26.9
26.9
Unit Nominal Run Amps
A
470.2
505.6
551.8
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
12.4
16.8
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
33.2
33.2
Unit Nominal Run Amps
A
475.8
510.6
556.8
Recommended Mains Fuse Size
A
560
560
630
Motor Rating
kW
16.8
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.