ELECTRICAL DATA

28

29

30

Unit Data

DCF073TR-13GPPY

DCF078TR-14GPYY

DCF082TR-13HYYV

Nominal Run Amps

(1)

A

454.6

484.2

530.6

Maximum Start Amps

A

689.9

719.5

759.0

Recommended Mains Fuse Size

A

500

560

560

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

13

14

13

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

13

14

13

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

13

14

13

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 59.2 / 47.5

59.2 / 47.5 / 47.5

47.5 / 47.5 / 55.2

Quantity

2 + 2 + 3

2 + 3 + 3

3 + 3 + 3

Motor Rating

kW

36.2 / 36.2 / 29.6

36.2 / 29.6 / 29.6

29.6 / 29.6 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 298 / 287

298 / 287 / 287

287 / 287 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

416.5

446.4

487.6

Reactive power reduction/saving

(4)

kVAr

65.1

65.4

73.8

Maximum Start Amps

A

651.8

681.7

716.0

Recommended Mains Fuse Size

A

500

560

560

Electronic Soft-start
Nominal Run Amps

A

454.6

484.2

530.6

Maximum Start Amps

A

570.7

600.3

644.2

Recommended Mains Fuse

A

500

560

560

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

416.5

446.4

487.6

Maximum Start Amps

A

532.6

562.5

601.2

Recommended Mains Fuse Size

A

500.0

560.0

560.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

28.5

28.5

Unit Nominal Run Amps

A

475.7

512.6

559.0

Recommended Mains Fuse Size

A

500

560

630

Motor Rating

kW

12.1

16.4

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

35.0

35.0

Unit Nominal Run Amps

A

483.0

519.1

565.5

Recommended Mains Fuse Size

A

560

560

630

Motor Rating

kW

16.4

20.3

20.3

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

19.8

26.9

26.9

Unit Nominal Run Amps

A

470.2

505.6

551.8

Recommended Mains Fuse Size

A

500

560

630

Motor Rating

kW

12.4

16.8

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

33.2

33.2

Unit Nominal Run Amps

A

475.8

510.6

556.8

Recommended Mains Fuse Size

A

560

560

630

Motor Rating

kW

16.8

20.7

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet