Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data - regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 134

Advertising
background image

134

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

ELECTRICAL DATA

13

14

15

Unit Data

DCF069TR-10GPPY

DCF051DR-11DXY0

DCF053DR-11DPY0

Nominal Run Amps

(1)

A

442.4

314.3

321.1

Maximum Start Amps

A

677.7

550.9

556.4

Recommended Mains Fuse Size

A

500

355

355

Evaporator
Immersion Heater Rating

W

250

170

170

Condenser Fan - Per Fan (AC)
Quantity

10

11

11

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

10

11

11

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

10

11

11

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 59.2 / 47.5

37.1 / 47.5

59.2 / 47.5

Quantity

2 + 2 + 3

3 + 3

2 + 3

Motor Rating

kW

36.2 / 36.2 / 29.6

23.5 / 29.6

36.2 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 298 / 287

210 / 287

298 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

407.3

291.9

293.7

Reactive power reduction/saving

(4)

kVAr

60.4

39.4

46.6

Maximum Start Amps

A

642.6

528.5

529.0

Recommended Mains Fuse Size

A

500

355

355

Electronic Soft-start
Nominal Run Amps

A

442.4

314.3

321.1

Maximum Start Amps

A

558.5

436.1

437.2

Recommended Mains Fuse

A

500

355

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

407.3

291.9

293.7

Maximum Start Amps

A

523.4

413.7

409.8

Recommended Mains Fuse Size

A

500.0

355.0

355.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

14.8

14.8

Unit Nominal Run Amps

A

470.8

329.0

335.8

Recommended Mains Fuse Size

A

500

355

355

Motor Rating

kW

16.4

8.4

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

21.2

21.2

Unit Nominal Run Amps

A

477.3

335.4

342.2

Recommended Mains Fuse Size

A

500

355

400

Motor Rating

kW

20.3

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

26.9

13.9

13.9

Unit Nominal Run Amps

A

463.7

325.4

332.0

Recommended Mains Fuse Size

A

500

355

355

Motor Rating

kW

16.8

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

19.8

19.8

Unit Nominal Run Amps

A

468.7

330.2

336.7

Recommended Mains Fuse Size

A

500

355

400

Motor Rating

kW

20.7

12.4

12.4

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet

Advertising
This manual is related to the following products: