Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data - regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 134
134
Chiller Technical Manual 7267818 V1.4.0_04_2014
Chillers
DeltaChill™ Air Cooled and FreeCool
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
13
14
15
Unit Data
DCF069TR-10GPPY
DCF051DR-11DXY0
DCF053DR-11DPY0
Nominal Run Amps
(1)
A
442.4
314.3
321.1
Maximum Start Amps
A
677.7
550.9
556.4
Recommended Mains Fuse Size
A
500
355
355
Evaporator
Immersion Heater Rating
W
250
170
170
Condenser Fan - Per Fan (AC)
Quantity
10
11
11
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
10
11
11
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
10
11
11
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 59.2 / 47.5
37.1 / 47.5
59.2 / 47.5
Quantity
2 + 2 + 3
3 + 3
2 + 3
Motor Rating
kW
36.2 / 36.2 / 29.6
23.5 / 29.6
36.2 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 298 / 287
210 / 287
298 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
407.3
291.9
293.7
Reactive power reduction/saving
(4)
kVAr
60.4
39.4
46.6
Maximum Start Amps
A
642.6
528.5
529.0
Recommended Mains Fuse Size
A
500
355
355
Electronic Soft-start
Nominal Run Amps
A
442.4
314.3
321.1
Maximum Start Amps
A
558.5
436.1
437.2
Recommended Mains Fuse
A
500
355
355
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
407.3
291.9
293.7
Maximum Start Amps
A
523.4
413.7
409.8
Recommended Mains Fuse Size
A
500.0
355.0
355.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
14.8
14.8
Unit Nominal Run Amps
A
470.8
329.0
335.8
Recommended Mains Fuse Size
A
500
355
355
Motor Rating
kW
16.4
8.4
8.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
21.2
21.2
Unit Nominal Run Amps
A
477.3
335.4
342.2
Recommended Mains Fuse Size
A
500
355
400
Motor Rating
kW
20.3
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
13.9
13.9
Unit Nominal Run Amps
A
463.7
325.4
332.0
Recommended Mains Fuse Size
A
500
355
355
Motor Rating
kW
16.8
8.6
8.6
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
19.8
19.8
Unit Nominal Run Amps
A
468.7
330.2
336.7
Recommended Mains Fuse Size
A
500
355
400
Motor Rating
kW
20.7
12.4
12.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet