Chillers

DeltaChill™ Air Cooled and FreeCool

31

Chiller Technical Manual 7267818 V1.4.0_04_2014

Introduction

Compressor Enclosures

Compressor enclosures shall be fitted to the extra quiet units.
Enclosures are fitted as standard when refrigerant leak detection is selected.

Control Panel Rain Hood

A rain hood shall be supplied to protect the control panel from certain weather conditions. An integral light shall be also

fitted.

Anti Vibration Mounts (Spring Type)

Spring vibration isolators can be supplied loose for on site

fitting to the base frame of each unit.

The isolators are suitable for fitting to structural steelwork

providing the surface is level and of sufficient strength

where a high level of vibration elimination is required.
The Spring vibration isolator requires an overall

clearance of 162 mm (unloaded) with a loaded dimension

(dependant on load) of 136 mm.

Anti Vibration Mounts (Pad Type)

Pad vibration isolators can be supplied loose for on site

fitting to the base frame of each unit.

The isolators are suitable for fitting to structural steelwork

providing the surface is level and of sufficient strength

where a moderate degree of vibration elimination is

required.