Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 197: Dcc performance data ec fans
![background image](/manuals/370937/197/background.png)
197
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
164
DCC075TX-15GYYY
5
795.4
208.8
751.2
231.3
703.2
257.0
651.6
285.9
6
818.7
210.4
773.2
232.9
723.8
258.7
670.8
287.7
7
842.2
212.0
795.4
234.6
744.7
260.5
690.3
289.6
8
865.9
213.6
817.9
236.4
765.9
262.4
710.1
291.5
9
889.9
215.3
840.7
238.2
787.3
264.2
730.1
293.4
10
914.1
217.1
863.7
240.0
809.0
266.1
750.4
295.4
165
DCC077TX-16GYYV
5
822.3
214.3
777.2
237.5
728.1
264.0
675.3
294.0
6
846.3
215.9
799.9
239.1
749.5
265.7
695.2
295.8
7
870.5
217.5
823.0
240.8
771.2
267.5
715.4
297.6
8
895.1
219.1
846.3
242.5
793.1
269.3
736.0
299.5
9
919.8
220.7
869.8
244.2
815.3
271.1
756.8
301.4
10
944.8
222.4
893.6
246.0
837.8
273.0
777.9
303.4
166
DCC072TX-17GPYY
5
759.4
188.3
719.8
208.0
676.4
230.7
629.4
256.4
6
781.8
189.5
741.1
209.3
696.5
232.1
648.2
257.8
7
804.4
190.7
762.7
210.6
717.0
233.4
667.3
259.3
8
827.2
192.0
784.6
212.0
737.6
234.9
686.7
260.7
9
850.3
193.3
806.6
213.4
758.6
236.3
706.4
262.3
10
873.5
194.6
828.9
214.8
779.7
237.8
726.4
263.8
167
DCC077TX-18GYYY
5
815.8
200.9
772.7
222.3
725.8
246.8
675.2
274.6
6
840.1
202.3
795.8
223.6
747.6
248.2
695.6
276.1
7
864.7
203.6
819.3
225.0
769.7
249.7
716.3
277.7
8
889.5
205.0
843.0
226.5
792.1
251.2
737.3
279.2
9
914.7
206.4
867.0
228.0
814.9
252.8
758.7
280.8
10
940.1
207.8
891.2
229.5
837.9
254.3
780.3
282.4
168
DCC080TX-17GYVV
5
849.2
219.9
803.2
243.7
753.1
271.0
698.9
302.0
6
873.9
221.4
826.7
245.3
775.2
272.7
719.6
303.8
7
898.9
222.9
850.5
246.9
797.6
274.4
740.6
305.7
8
924.2
224.5
874.6
248.6
820.4
276.2
761.8
307.5
9
949.7
226.1
898.9
250.3
843.4
278.0
783.4
309.4
10
975.5
227.8
923.5
252.1
866.6
279.9
805.3
311.4
169
DCC083TX-18GVVV
5
876.0
225.5
829.2
249.9
778.0
278.0
722.6
310.1
6
901.5
226.9
853.5
251.4
800.9
279.7
744.0
311.9
7
927.3
228.4
878.1
253.0
824.1
281.4
765.7
313.7
8
953.4
230.0
902.9
254.7
847.6
283.1
787.7
315.5
9
979.7
231.5
928.1
256.4
871.4
284.9
810.0
317.4
10
1006.2
233.1
953.4
258.1
895.4
286.8
832.7
319.4
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans