Chillers deltachill™ air cooled and freecool, Desi gn, Design data – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 55: Correction factors

Advertising
background image

55

Chiller Technical Manual 7267818 V1.4.0_04_2014

D

esi

gn

Chillers

DeltaChill™ Air Cooled and FreeCool

Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be

exposed to freezing temperatures (lower than 3°C Ambient). This is specified further in the environmental consideration

section at the front of this document.

Glycol Percentage / Freezing Point

Temperature °C

0% / °C

20% / -7.1°C

25% / -9.6°C

30% / -12.7°C

35% / -16.4°C

40% / -21.1°C

0

4.21

3.93

3.86

3.79

3.72

3.64

5

4.20

3.94

3.87

3.81

3.73

3.65

10

4.19

3.95

3.89

3.82

3.75

3.67

15

4.19

3.96

3.90

3.83

3.76

3.69

20

4.18

3.97

3.91

3.85

3.78

3.70

25

4.18

3.98

3.92

3.86

3.79

3.72

30

4.18

3.99

3.94

3.88

3.81

3.74

35

4.18

4.01

3.95

3.89

3.82

3.75

40

4.18

4.02

3.96

3.90

3.84

3.77

45

4.18

4.03

3.97

3.92

3.85

3.78

Glycol Percentage / Freezing Point

Temperature °C

0% / °C

20% / -7.1°C

25% / -9.6°C

30% / -12.7°C

35% / -16.4°C

40% / -21.1°C

0

999.8

1025.8

1031.0

1036.2

1040.7

1045.1

5

999.9

1024.3

1029.4

1034.5

1038.8

1043.1

10

999.7

1022.7

1027.6

1032.6

1036.8

1040.9

15

999.0

1020.9

1025.7

1030.5

1034.6

1038.7

20

998.2

1019.0

1023.7

1028.4

1032.3

1036.2

25

997.0

1017.0

1021.5

1026.1

1029.9

1033.7

30

995.6

1014.8

1019.2

1023.6

1027.3

1031.0

35

994.0

1012.6

1016.8

1021.1

1024.7

1028.2

40

992.2

1010.2

1014.3

1018.4

1021.9

1025.3

45

990.2

1007.6

1011.6

1015.6

1018.9

1022.2

Propylene Glycol Specific Heat

Propylene Glycol Density

Glycol

Design Data

Kw =ρ x m x Cp x ∆t

Where

kW = Cooling Performance (KW)

ρ =

Density of cooling medium (kg/m³)

m = mass flow of cooling media (kg/s)

Cp = Specific heat Capacity (kj/kg K)

∆t = Temperature difference between Inlet and Outlet (K)

Glycol in System / Freezing Point ºC

10% / -2°C

20% / -6°C

30% / -12°C

40% / -20°C

Cooling Duty

Catalogue Data x by:

0.97

0.95

0.91

0.88

Input Power

0.99

0.98

0.96

0.95

Water Flow

0.98

0.97

0.95

0.95

Pressure Drop

1.08

1.17

1.31

1.45

Correction Factors