Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf performance data ac fans – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 70

Advertising
background image

70

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

71 DCF068DX-14FWW0

6

679.9

176.6

642.1

193.9

600.9

213.5

556.6

235.5

7

699.2

177.9

660.4

195.3

618.1

214.9

572.4

237.1

8

718.8

179.2

678.9

196.7

635.4

216.5

588.6

238.6

10

758.6

182.0

716.6

199.7

670.8

219.6

621.5

241.9

12

799.1

184.9

755.1

202.8

707.0

222.8

655.3

245.2

14

840.4

187.8

794.3

205.9

744.0

226.2

690.0

248.7

72 DCF069TX-13GPPY

6

708.6

194.9

667.4

214.6

622.9

236.9

575.1

262.0

7

728.6

196.5

686.2

216.3

640.4

238.7

591.3

263.8

8

748.8

198.1

705.3

218.1

658.2

240.6

607.8

265.7

10

789.9

201.6

744.0

221.7

694.4

244.3

641.4

269.6

12

831.7

205.1

783.5

225.5

731.4

248.3

675.8

273.6

14

874.3

208.8

823.7

229.4

769.2

252.4

711.1

277.9

73 DCF075TX-14GPYY

6

762.1

208.3

717.8

229.8

670.1

254.1

619.1

281.3

7

783.8

210.0

738.3

231.6

689.2

255.9

636.7

283.2

8

805.7

211.8

758.9

233.4

708.6

257.9

654.7

285.2

10

850.3

215.4

801.0

237.2

747.9

261.8

691.2

289.3

12

895.7

219.2

843.9

241.2

788.2

266.0

728.8

293.6

14

942.0

223.1

887.7

245.3

829.4

270.3

767.3

298.0

74 DCF059DX-15DYV0

6

586.0

145.9

555.8

160.6

523.1

177.6

487.9

196.9

7

603.4

146.7

572.4

161.5

538.8

178.5

502.6

197.8

8

620.9

147.5

589.2

162.4

554.7

179.4

517.5

198.8

10

656.8

149.2

623.5

164.1

587.3

181.3

548.2

200.7

12

693.4

151.0

658.6

166.0

620.6

183.2

579.7

202.8

14

730.8

152.9

694.4

168.0

654.8

185.3

612.0

204.9

75 DCF061DX-16DVV0

6

611.6

152.7

580.5

168.1

546.6

185.9

510.1

206.3

7

629.7

153.4

597.7

168.9

563.0

186.8

525.4

207.2

8

647.9

154.2

615.2

169.8

579.6

187.7

541.0

208.2

10

685.2

155.9

650.9

171.5

613.5

189.6

573.0

210.1

12

723.3

157.6

687.4

173.4

648.3

191.5

605.9

212.2

14

762.1

159.4

724.7

175.3

683.9

193.5

639.6

214.3

76 DCF066DX-16FVW0

6

660.3

163.3

625.4

179.4

587.4

197.8

546.4

218.7

7

679.6

164.2

643.8

180.4

604.8

198.9

562.6

219.8

8

699.2

165.3

662.4

181.5

622.4

200.0

579.1

221.0

10

739.1

167.3

700.4

183.7

658.3

202.4

612.8

223.5

12

779.8

169.5

739.4

186.0

695.2

204.8

647.4

226.0

14

821.4

171.7

779.1

188.4

732.9

207.3

683.0

228.7

77 DCF069DX-16FWW0

6

692.5

173.2

655.5

189.9

615.1

208.9

571.3

230.4

7

712.5

174.3

674.5

191.1

632.9

210.2

587.9

231.7

8

732.8

175.5

693.7

192.4

651.0

211.6

604.8

233.1

10

773.9

177.9

732.9

195.0

688.0

214.3

639.4

236.0

12

816.0

180.4

773.0

197.7

725.9

217.2

674.9

238.9

14

858.8

182.9

813.9

200.5

764.6

220.1

711.3

242.0

1

Output kW refers to the chilled water duty (Based upon 20% Ethylene Glycol).

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

DCF Performance Data AC Fans

Advertising
This manual is related to the following products: