ELECTRICAL DATA
58
59
60
Unit Data
DCF053DX-12DPV0
DCF055DX-11DYV0
DCF055DX-12DYY0
Nominal Run Amps
(1)
A
330.4
353.4
331.2
Maximum Start Amps
A
565.7
581.8
567.8
Recommended Mains Fuse Size
A
355
400
355
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
12
11
12
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
12
11
12
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 55.2
47.5 / 55.2
47.5 / 47.5
Quantity
2 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 33.1
29.6 / 33.1
29.6 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 267
287 / 267
287 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
300.7
325.7
310.3
Reactive power reduction/saving
(4)
kVAr
49.9
47.9
37.4
Maximum Start Amps
A
536.0
554.1
546.9
Recommended Mains Fuse Size
A
355
400
355
Electronic Soft-start
Nominal Run Amps
A
330.4
353.4
331.2
Maximum Start Amps
A
446.5
467.0
453.0
Recommended Mains Fuse
A
355
400
355
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
300.7
325.7
310.3
Maximum Start Amps
A
416.8
439.3
432.1
Recommended Mains Fuse Size
A
355
400
355
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
21.2
14.8
Unit Nominal Run Amps
A
345.1
374.5
345.8
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
8.4
12.1
8.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
28.5
21.2
Unit Nominal Run Amps
A
351.5
381.8
352.2
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
12.1
16.4
12.1
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
13.9
19.8
13.9
Unit Nominal Run Amps
A
341.2
369.2
342.3
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
8.6
12.4
8.6
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
26.9
19.8
Unit Nominal Run Amps
A
345.9
374.8
347.2
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
12.4
16.8
12.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet