Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 149: Dcf electrical data extra quiet

Advertising
background image

149

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

58

59

60

Unit Data

DCF053DX-12DPV0

DCF055DX-11DYV0

DCF055DX-12DYY0

Nominal Run Amps

(1)

A

330.4

353.4

331.2

Maximum Start Amps

A

565.7

581.8

567.8

Recommended Mains Fuse Size

A

355

400

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

12

11

12

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

12

11

12

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 55.2

47.5 / 55.2

47.5 / 47.5

Quantity

2 + 3

3 + 3

3 + 3

Motor Rating

kW

36.2 / 33.1

29.6 / 33.1

29.6 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 267

287 / 267

287 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

300.7

325.7

310.3

Reactive power reduction/saving

(4)

kVAr

49.9

47.9

37.4

Maximum Start Amps

A

536.0

554.1

546.9

Recommended Mains Fuse Size

A

355

400

355

Electronic Soft-start
Nominal Run Amps

A

330.4

353.4

331.2

Maximum Start Amps

A

446.5

467.0

453.0

Recommended Mains Fuse

A

355

400

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

300.7

325.7

310.3

Maximum Start Amps

A

416.8

439.3

432.1

Recommended Mains Fuse Size

A

355

400

355

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

21.2

14.8

Unit Nominal Run Amps

A

345.1

374.5

345.8

Recommended Mains Fuse Size

A

400

400

400

Motor Rating

kW

8.4

12.1

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

28.5

21.2

Unit Nominal Run Amps

A

351.5

381.8

352.2

Recommended Mains Fuse Size

A

400

400

400

Motor Rating

kW

12.1

16.4

12.1

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

13.9

19.8

13.9

Unit Nominal Run Amps

A

341.2

369.2

342.3

Recommended Mains Fuse Size

A

400

400

400

Motor Rating

kW

8.6

12.4

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

26.9

19.8

Unit Nominal Run Amps

A

345.9

374.8

347.2

Recommended Mains Fuse Size

A

400

400

400

Motor Rating

kW

12.4

16.8

12.4

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet