Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 181: Dcc performance data ac fans
![background image](/manuals/370937/181/background.png)
181
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
152
DCC052DX-14EYY0
5
544.0
135.2
517.4
148.8
488.0
164.5
456.0
182.5
6
560.1
135.9
532.9
149.5
502.8
165.3
469.9
183.3
7
576.3
136.6
548.6
150.3
517.7
166.1
484.0
184.1
8
592.8
137.4
564.4
151.0
532.8
166.9
498.3
185.0
9
609.3
138.1
580.4
151.8
548.1
167.7
512.8
185.8
10
626.0
138.9
596.5
152.6
563.6
168.5
527.5
186.7
153
DCC054DX-13DYV0
5
573.5
144.5
544.2
159.3
511.9
176.4
477.0
195.9
6
590.3
145.3
560.3
160.2
527.2
177.3
491.3
196.9
7
607.4
146.2
576.6
161.1
542.2
178.4
505.8
197.9
8
624.6
147.0
593.1
162.0
558.3
179.2
520.6
198.9
9
641.9
147.9
609.8
162.9
574.2
180.2
535.6
199.9
10
659.5
148.8
626.6
163.9
590.2
181.2
550.7
201.0
154
DCC057DX-14DVV0
5
607.2
151.3
576.1
166.8
542.0
184.7
504.9
205.2
6
625.1
152.1
593.2
167.6
558.2
185.6
520.2
206.2
7
643.2
152.9
610.6
168.5
574.6
186.6
535.6
207.2
8
661.5
153.8
628.1
169.4
591.3
187.5
551.3
208.3
9
680.0
154.6
645.8
170.4
608.1
188.5
567.2
209.3
10
698.7
155.5
663.8
171.3
625.2
189.5
583.3
210.4
155
DCC060DX-14DVW0
5
633.9
160.9
601.2
177.0
565.0
195.6
525.6
216.7
6
652.3
161.9
618.7
178.1
581.6
196.7
541.2
217.8
7
671.0
162.9
636.5
179.1
598.5
197.8
557.0
219.0
8
689.8
163.9
654.5
180.2
615.5
199.0
573.0
220.2
9
708.7
164.9
672.7
181.3
632.8
200.2
589.2
221.5
10
727.8
165.9
691.0
182.5
650.2
201.4
605.7
222.7
156
DCC063DX-14DWW0
5
672.6
171.2
636.9
187.9
597.5
207.1
554.7
228.7
6
692.0
172.4
655.3
189.2
614.8
208.4
570.9
230.1
7
711.6
173.6
674.0
190.5
632.4
209.8
587.3
231.5
8
731.4
174.8
692.8
191.8
650.2
211.2
603.9
233.0
9
751.3
176.0
711.9
193.1
668.2
212.6
620.8
234.4
10
771.5
177.2
731.1
194.5
686.4
214.0
637.9
235.9
157
DCC066TX-13GPPY
5
705.5
188.3
666.1
207.4
623.0
229.1
576.7
253.6
6
725.8
189.8
685.3
208.9
641.0
230.7
593.4
255.3
7
745.6
191.5
703.8
210.8
659.2
232.4
610.3
257.0
8
767.1
192.7
724.4
212.1
677.7
234.0
627.5
258.7
9
788.1
194.3
744.3
213.7
696.4
235.8
644.9
260.4
10
809.2
195.8
764.3
215.4
715.3
237.5
662.6
262.2
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data AC Fans