Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data extra quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 148

Advertising
background image

148

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

DCF Electrical Data Extra Quiet

ELECTRICAL DATA

55

56

57

Unit Data

DCF053DX-10DYY0

DCF049DX-11DXY0

DCF051DX-11DPY0

Nominal Run Amps

(1)

A

326.4

296.5

303.0

Maximum Start Amps

A

563.0

533.1

538.3

Recommended Mains Fuse Size

A

355

315

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

10

11

11

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

10

11

11

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5

37.1 / 47.5

59.2 / 47.5

Quantity

3 + 3

3 + 3

2 + 3

Motor Rating

kW

29.6 / 29.6

23.5 / 29.6

36.2 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287

210 / 287

298 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

306.5

279.7

281.5

Reactive power reduction/saving

(4)

kVAr

35.9

30.7

37.9

Maximum Start Amps

A

543.1

516.3

516.8

Recommended Mains Fuse Size

A

355

315

355

Electronic Soft-start
Nominal Run Amps

A

326.4

296.5

303.0

Maximum Start Amps

A

448.2

418.3

419.1

Recommended Mains Fuse

A

355

315

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

306.5

279.7

281.5

Maximum Start Amps

A

428.3

401.5

397.6

Recommended Mains Fuse Size

A

355

315

355

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

14.8

14.8

Unit Nominal Run Amps

A

341.0

311.2

317.7

Recommended Mains Fuse Size

A

355

355

355

Motor Rating

kW

8.4

8.4

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

347.4

317.5

324.1

Recommended Mains Fuse Size

A

400

355

355

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

13.9

Unit Nominal Run Amps

A

337.5

307.7

314.1

Recommended Mains Fuse Size

A

355

355

355

Motor Rating

kW

8.6

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

342.4

312.6

318.9

Recommended Mains Fuse Size

A

400

355

355

Motor Rating

kW

12.4

12.4

12.4

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.