Unit Data
DCC059DR-14DVV0
DCC061DR-14DVW0
DCC065DR-14DWW0
Nominal Run Amps
(1)
A
409.2
421.2
433.3
Maximum Start Amps
A
617.6
656.5
668.6
Recommended Mains Fuse Size
A
450
450
500
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
14
14
14
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
14
14
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2
55.2 / 59.2
59.2 / 59.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
33.1 / 33.1
33.1 / 36.2
36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 267
267 / 298
298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
364.3
378.5
392.6
Reactive power reduction/saving
(4)
kVAr
72.4
70.1
67.8
Maximum Start Amps
A
572.7
613.8
627.9
Recommended Mains Fuse Size
A
450
450
500
Electronic Soft-start
Nominal Run Amps
A
409.2
421.2
433.3
Maximum Start Amps
A
510.8
537.3
549.4
Recommended Mains Fuse
A
450
450
500
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
364.3
378.5
392.6
Maximum Start Amps
A
465.9
494.6
508.7
Recommended Mains Fuse Size
A
450
450
500
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
420.4
432.3
444.4
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
6.2
6.2
6.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
14.8
21.2
Unit Nominal Run Amps
A
420.4
436.0
454.4
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
6.1
8.4
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
10.2
10.2
Unit Nominal Run Amps
A
417.0
429.1
441.2
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
6.4
6.4
6.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
10.1
13.9
19.8
Unit Nominal Run Amps
A
416.9
431.9
448.7
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
6.3
8.6
12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold