Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
70
71
72
Unit Data
DCF064DX-14FVW0
DCF068DX-14FWW0
DCF069TX-13GPPY
Nominal Run Amps
(1)
A
397.9
410.1
433.3
Maximum Start Amps
A
633.2
645.4
668.6
Recommended Mains Fuse Size
A
450
450
500
Evaporator
Immersion Heater Rating
W
170
170
250
Condenser Fan - Per Fan (AC)
Quantity
14
14
13
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
14
14
13
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2
59.2 / 59.2
59.2 / 59.2 / 47.5
Quantity
3 + 3
3 + 3
2 + 2 + 3
Motor Rating
kW
33.1 / 36.2
36.2 / 36.2
36.2 / 36.2 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 298
298 / 298
298 / 298 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
362.9
377.1
402.0
Reactive power reduction/saving
(4)
kVAr
59.1
56.8
54.8
Maximum Start Amps
A
598.2
612.4
637.3
Recommended Mains Fuse Size
A
450
450
500
Electronic Soft-start
Nominal Run Amps
A
397.9
410.1
433.3
Maximum Start Amps
A
514.0
526.2
549.4
Recommended Mains Fuse
A
450
450
500
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
362.9
377.1
402.0
Maximum Start Amps
A
479.0
493.2
518.1
Recommended Mains Fuse Size
A
450
450
500
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
419.0
431.2
454.4
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
426.3
438.5
461.7
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
413.5
425.8
449.1
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
419.1
431.4
454.8
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet