ELECTRICAL DATA

70

71

72

Unit Data

DCF064DX-14FVW0

DCF068DX-14FWW0

DCF069TX-13GPPY

Nominal Run Amps

(1)

A

397.9

410.1

433.3

Maximum Start Amps

A

633.2

645.4

668.6

Recommended Mains Fuse Size

A

450

450

500

Evaporator
Immersion Heater Rating

W

170

170

250

Condenser Fan - Per Fan (AC)
Quantity

14

14

13

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

14

14

13

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 59.2

59.2 / 59.2

59.2 / 59.2 / 47.5

Quantity

3 + 3

3 + 3

2 + 2 + 3

Motor Rating

kW

33.1 / 36.2

36.2 / 36.2

36.2 / 36.2 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 298

298 / 298

298 / 298 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

362.9

377.1

402.0

Reactive power reduction/saving

(4)

kVAr

59.1

56.8

54.8

Maximum Start Amps

A

598.2

612.4

637.3

Recommended Mains Fuse Size

A

450

450

500

Electronic Soft-start
Nominal Run Amps

A

397.9

410.1

433.3

Maximum Start Amps

A

514.0

526.2

549.4

Recommended Mains Fuse

A

450

450

500

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

362.9

377.1

402.0

Maximum Start Amps

A

479.0

493.2

518.1

Recommended Mains Fuse Size

A

450

450

500

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

419.0

431.2

454.4

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

12.1

12.1

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

426.3

438.5

461.7

Recommended Mains Fuse Size

A

450

500

500

Motor Rating

kW

16.4

16.4

16.4

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

413.5

425.8

449.1

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

12.4

12.4

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

419.1

431.4

454.8

Recommended Mains Fuse Size

A

450

500

500

Motor Rating

kW

16.8

16.8

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet