Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 147: Dcf electrical data extra quiet

Advertising
background image

147

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

52

53

54

Unit Data

DCF047DX-09DXY0

DCF049DX-09DPY0

DCF051DX-10DPV0

Nominal Run Amps

(1)

A

291.7

298.2

325.5

Maximum Start Amps

A

528.3

533.5

560.8

Recommended Mains Fuse Size

A

315

315

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

9

9

10

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

9

9

10

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

37.1 / 47.5

59.2 / 47.5

59.2 / 55.2

Quantity

3 + 3

2 + 3

2 + 3

Motor Rating

kW

23.5 / 29.6

36.2 / 29.6

36.2 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

210 / 287

298 / 287

298 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

275.8

277.6

296.9

Reactive power reduction/saving

(4)

kVAr

29.2

36.4

48.3

Maximum Start Amps

A

512.4

512.9

532.2

Recommended Mains Fuse Size

A

315

315

355

Electronic Soft-start
Nominal Run Amps

A

291.7

298.2

325.5

Maximum Start Amps

A

413.5

414.3

441.6

Recommended Mains Fuse

A

315

315

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

275.8

277.6

296.9

Maximum Start Amps

A

397.6

393.7

413.0

Recommended Mains Fuse Size

A

315

315

355

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

14.8

14.8

Unit Nominal Run Amps

A

306.4

312.9

340.2

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

8.4

8.4

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

312.7

319.3

346.6

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

13.9

Unit Nominal Run Amps

A

303.0

309.3

336.3

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

8.6

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

307.9

314.1

341.1

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

12.4

12.4

12.4

DCF Electrical Data Extra Quiet

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.