Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 147: Dcf electrical data extra quiet
147
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
52
53
54
Unit Data
DCF047DX-09DXY0
DCF049DX-09DPY0
DCF051DX-10DPV0
Nominal Run Amps
(1)
A
291.7
298.2
325.5
Maximum Start Amps
A
528.3
533.5
560.8
Recommended Mains Fuse Size
A
315
315
355
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
9
9
10
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
9
9
10
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
37.1 / 47.5
59.2 / 47.5
59.2 / 55.2
Quantity
3 + 3
2 + 3
2 + 3
Motor Rating
kW
23.5 / 29.6
36.2 / 29.6
36.2 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
210 / 287
298 / 287
298 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
275.8
277.6
296.9
Reactive power reduction/saving
(4)
kVAr
29.2
36.4
48.3
Maximum Start Amps
A
512.4
512.9
532.2
Recommended Mains Fuse Size
A
315
315
355
Electronic Soft-start
Nominal Run Amps
A
291.7
298.2
325.5
Maximum Start Amps
A
413.5
414.3
441.6
Recommended Mains Fuse
A
315
315
355
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
275.8
277.6
296.9
Maximum Start Amps
A
397.6
393.7
413.0
Recommended Mains Fuse Size
A
315
315
355
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
14.8
Unit Nominal Run Amps
A
306.4
312.9
340.2
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
8.4
8.4
8.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
312.7
319.3
346.6
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
12.1
12.1
12.1
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
13.9
Unit Nominal Run Amps
A
303.0
309.3
336.3
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
8.6
8.6
8.6
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
307.9
314.1
341.1
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
12.4
12.4
12.4
DCF Electrical Data Extra Quiet
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.