Installation Data
Weights, Point Loadings & Centre of Gravity (C of G) DCC
Point loads
L1
L2
L3
L4
L5
L6
L7
R1
R2
R3
R4
R5
R6
R7
C of
G 1 C of G 2
kg
mm
mm
98
DCC047DR-08EPV0
500
570
625
705
805
885
1280
2475
99
DCC049DR-08EYY0
530
570
605
780
840
890
1300
2390
100
DCC049DR-10EPV0
500
490
485
475
680
670
660
650
1260
2780
101
DCC051DR-10EYY0
520
500
480
460
735
705
680
650
1280
2690
102
DCC052DR-09DYV0
530
505
490
470
740
710
685
655
1275
2690
103
DCC056DR-10DVV0
535
510
495
470
755
720
695
665
1280
2680
104
DCC058DR-10DVW0
535
510
495
475
760
725
700
670
1280
2685
105
DCC061DR-10DWW0
540
515
495
470
770
735
705
675
1285
2680
106
DCC065TR-10GPPY
555
580
595
615
745
775
795
825
1250
2965
107
DCC050DR-12EPV0
585
570
555
535
765
745
725
700
1240
3275
108
DCC052DR-12EYY0
605
580
555
520
815
785
750
705
1260
3185
109
DCC054DR-11DYV0
605
585
560
535
820
790
755
720
1255
3215
110
DCC058DR-12DVV0
620
590
565
530
840
805
765
720
1260
3170
111
DCC060DR-12DVW0
620
590
565
530
845
810
770
725
1265
3175
112
DCC063DR-12DWW0
620
595
565
530
855
815
775
730
1265
3165
113
DCC069TR-11GPYY
635
640
645
645
895
900
905
910
1275
3430
114
DCC074TR-12GYYY
675
665
650
635
970
955
935
910
1290
3310
115
DCC056DR-13DYV0
550
525
495
525
450
720
685
650
685
590
1240
3615
116
DCC059DR-14DVV0
555
525
500
525
450
730
695
660
695
590
1245
3600
117
DCC061DR-14DVW0
555
530
500
530
450
735
700
660
700
595
1245
3595
118
DCC065DR-14DWW0
555
530
500
530
450
740
705
665
705
600
1250
3585
119
DCC068TR-13GPPY
590
575
560
575
530
770
750
725
750
690
1235
3775
120
DCC072TR-14GPYY
600
585
570
585
540
805
785
760
785
720
1250
3775
121
DCC077TR-13GYYV
625
600
575
600
525
855
820
785
820
715
1260
3660
122
DCC080TR-14GYVV
635
610
580
610
535
865
830
795
830
730
1260
3665
123
DCC070TR-16GPPY
660
625
580
625
520
855
805
750
805
675
1235
4150
124
DCC077TR-15GYYY
705
655
600
655
520
950
880
805
880
700
1255
4015
125
DCC080TR-16GYYV
715
665
605
665
525
965
890
815
890
705
1255
3985
126
DCC083TR-15GVVV
710
655
600
655
520
965
895
815
895
710
1260
4000
127
DCC086TR-15GVVW
710
660
600
660
525
970
900
820
900
715
1260
4005
(1) Point load numbering starts from the control panel end of the chiller. Illustration above is for a 8 mount configuration
(2) Point loads indicated are for standard unit only
2
1
L1
L2
L3
L4
R1
R2
R3
R4
= C of G