Introduction

Environmental Considerations

Freeze Protection

Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes

the units subject to low ambient temperatures. The DeltaChill freecool (DCF) chillers must have a minimum of 20%

glycol as standard.

Units with supply water temperatures below +5°C

Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be

exposed to freezing temperatures.

Units subject to ambient temperatures lower than 0°C

Glycol of an appropriate concentration (1) is used within the system to ensure adequate protection. Please ensure that

the concentration is capable of protection at least 3°C lower than ambient.

Water / glycol solution is constantly circulated through all waterside pipework and coils to avoid static water from

freezing.

Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C of the

solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).

Additional trace heating is provided for interconnecting pipework.

(1) Refer to your glycol supplier for details

Environmental Policy

It is our policy to:

Take a proactive approach to resolve environmental issues and ensure compliance with regulatory

requirements

Train personnel in sound environmental practices

Pursue opportunities to conserve resources, prevent pollution and eliminate waste

Manufacture products in a responsible manner with minimum impact on the environment

Reduce our use of chemicals and minimise their release to the environment

Measure, control and verify environmental performance through internal and external audits

Continually improve our environmental performance

CE Directive

Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:

Electromagnetic Compatibility Directive (EMC)

2004/108/EC

Low Voltage Directive (LVD)

2006/95/EC

Machinery Directive (MD)

89/392/EEC version 2006/42/EC

Pressure Equipment Directive (PED)

97/23/EC


To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the

Declaration of Conformity, supplied with each product.