Introduction
Environmental Considerations
Freeze Protection
Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes
the units subject to low ambient temperatures. The DeltaChill freecool (DCF) chillers must have a minimum of 20%
glycol as standard.
Units with supply water temperatures below +5°C
Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be
exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
Glycol of an appropriate concentration (1) is used within the system to ensure adequate protection. Please ensure that
the concentration is capable of protection at least 3°C lower than ambient.
Water / glycol solution is constantly circulated through all waterside pipework and coils to avoid static water from
freezing.
Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C of the
solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).
Additional trace heating is provided for interconnecting pipework.
(1) Refer to your glycol supplier for details
Environmental Policy
It is our policy to:
•
Take a proactive approach to resolve environmental issues and ensure compliance with regulatory
requirements
•
Train personnel in sound environmental practices
•
Pursue opportunities to conserve resources, prevent pollution and eliminate waste
•
Manufacture products in a responsible manner with minimum impact on the environment
•
Reduce our use of chemicals and minimise their release to the environment
•
Measure, control and verify environmental performance through internal and external audits
•
Continually improve our environmental performance
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
Electromagnetic Compatibility Directive (EMC)
2004/108/EC
Low Voltage Directive (LVD)
2006/95/EC
Machinery Directive (MD)
89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED)
97/23/EC
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.