Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 73: Dcf performance data ac fans
![background image](/manuals/370937/73/background.png)
73
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
92 DCF084TX-21GYYY
6
844.7
209.0
800.6
230.0
752.8
254.1
701.4
281.5
7
869.8
210.2
824.5
231.2
775.4
255.4
722.6
282.9
8
895.1
211.5
848.7
232.6
798.3
256.8
744.1
284.3
10
946.8
214.1
898.1
235.3
845.1
259.7
788.1
287.2
12
999.7
216.9
948.7
238.2
893.2
262.7
833.4
290.3
14
1053.7
219.8
1000.4
241.2
942.4
265.8
879.9
293.6
93 DCF087TX-22HYYV
6
868.8
215.6
825.1
237.4
777.3
262.5
725.5
291.0
7
894.2
216.8
849.4
238.7
800.3
263.8
747.2
292.4
8
919.8
218.0
873.9
240.0
823.7
265.1
769.1
293.8
10
971.8
220.6
923.9
242.6
871.3
267.9
814.1
296.7
12
1024.9
223.2
975.0
245.4
920.0
270.9
860.3
299.8
14
1078.7
226.0
1026.9
248.3
969.7
273.9
907.6
303.0
94 DCF092TX-21HVVV
6
923.2
233.5
874.8
257.6
822.1
285.2
765.1
316.7
7
949.9
234.9
900.3
259.0
846.2
286.8
787.6
318.4
8
977.0
236.3
926.1
260.6
870.6
288.4
810.5
320.1
10
1032.0
239.2
978.6
263.7
920.4
291.7
857.4
323.7
12
1088.1
242.3
1032.3
267.0
971.4
295.2
905.5
327.4
14
1145.2
245.5
1087.1
270.4
1023.5
298.9
954.8
331.2
95 DCF095TX-21HVVW
6
953.1
243.8
902.6
268.5
847.5
296.8
787.8
328.9
7
980.3
245.4
928.5
270.2
872.0
298.6
810.7
330.8
8
1007.8
247.0
954.8
271.9
896.8
300.4
834.0
332.7
10
1063.8
250.2
1008.2
275.4
947.4
304.2
881.4
336.6
12
1120.8
253.7
1062.8
279.1
999.1
308.1
930.2
340.8
14
1178.7
257.2
1118.2
282.9
1051.9
312.1
980.2
345.1
96 DCF097TX-21HVWW
6
982.9
254.1
930.4
279.4
872.9
308.4
810.6
341.1
7
1010.6
255.8
956.8
281.3
897.8
310.3
833.8
343.1
8
1038.7
257.6
983.6
283.3
923.0
312.4
857.4
345.2
10
1095.7
261.2
1037.9
287.2
974.4
316.6
905.5
349.6
12
1153.5
265.0
1093.2
291.3
1026.8
320.9
954.9
354.1
14
1212.1
268.9
1149.4
295.5
1080.4
325.4
1005.5
358.9
97 DCF099TX-21HWWW
6
1004.5
263.8
950.6
289.8
891.4
319.3
827.1
352.6
7
1032.7
265.7
977.4
291.9
916.6
321.5
850.5
354.8
8
1061.1
267.6
1004.5
294.0
942.1
323.7
874.3
357.1
10
1118.9
271.7
1059.5
298.3
994.0
328.3
922.8
361.9
12
1177.5
275.8
1115.5
302.8
1047.0
333.1
972.7
366.8
14
1236.8
280.0
1172.3
307.4
1101.1
338.0
1023.7
372.0
DCF Performance Data AC Fans
1
Output kW refers to the chilled water duty (Based upon 20% Ethylene Glycol).
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.