Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 172: Technical data dcc, Dcc performance data ac fans
172
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
DCC Performance Data AC Fans
Technical Data DCC
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
98
DCC047DR-08EPV0
5
502.3
139.9
475.3
153.7
445.4
169.7
413.0
187.9
6
516.6
140.8
488.9
154.7
458.2
170.8
424.9
189.1
7
531.0
141.8
502.6
155.8
471.1
172.0
437.0
190.2
8
545.6
142.8
516.5
156.9
484.2
173.1
449.3
191.4
9
560.2
143.8
530.5
158.0
497.4
174.3
461.7
192.6
10
575.0
144.9
544.6
159.1
510.8
175.5
474.3
193.8
99
DCC049DR-08EYY0
5
518.0
145.9
490.3
160.8
459.6
178.0
426.5
197.3
6
533.0
147.0
504.4
161.9
472.9
179.1
438.9
198.4
7
548.0
148.0
518.8
163.0
486.4
180.3
451.6
199.7
8
563.2
149.1
533.2
164.2
500.0
181.5
464.4
200.9
9
578.6
150.2
547.8
165.3
513.9
182.7
477.4
202.2
10
594.0
151.3
562.6
166.5
527.8
184.0
490.6
203.5
100
DCC049DR-10EPV0
5
517.9
135.5
492.1
148.4
463.2
163.6
431.4
180.9
6
532.9
136.2
506.6
149.2
476.8
164.4
444.2
181.8
7
548.1
137.0
521.2
150.1
490.7
165.3
457.3
182.8
8
563.5
137.8
535.9
150.9
504.7
166.2
470.5
183.7
9
579.0
138.6
550.8
151.8
518.9
167.1
483.9
184.7
10
594.5
139.4
565.8
152.6
533.2
168.1
497.5
185.6
101
DCC051DR-10EYY0
5
533.5
141.1
506.9
155.0
477.2
171.2
444.8
189.7
6
549.2
141.9
521.9
155.8
491.4
172.1
458.1
190.6
7
565.0
142.8
537.1
156.7
505.8
173.0
471.7
191.6
8
581.0
143.6
552.4
157.6
520.4
174.0
485.4
192.6
9
597.1
144.5
567.9
158.5
535.1
175.0
499.3
193.6
10
613.4
145.4
583.5
159.5
550.0
175.9
513.5
194.6
102
DCC052DR-09DYV0
5
557.9
152.4
528.3
167.8
495.5
185.6
460.0
205.9
6
574.1
153.4
543.6
168.8
509.9
186.8
473.5
207.1
7
590.4
154.4
559.1
169.9
524.5
187.9
487.3
208.3
8
606.8
155.5
574.8
171.1
539.4
189.1
501.2
209.5
9
623.5
156.5
590.7
172.2
554.4
190.3
515.3
210.8
10
640.2
157.6
606.7
173.4
569.5
191.6
529.6
212.0
103
DCC056DR-10DVV0
5
593.9
158.5
562.7
174.4
528.1
192.9
490.6
214.1
6
611.2
159.5
579.1
175.4
543.6
194.0
505.1
215.3
7
628.7
160.5
595.8
176.5
559.3
195.2
519.9
216.5
8
646.4
161.5
612.7
177.6
575.3
196.3
534.9
217.7
9
664.2
162.5
629.7
178.7
591.4
197.5
550.1
219.0
10
682.3
163.5
646.9
179.8
607.8
198.7
565.5
220.2
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.