Introduction

Chiller Technical Manual 7267818 V1.4.0_04_2014

DeltaChill™ Air Cooled and FreeCool

1. Clamp
2. Gasket
3. Counter pipe

1

2

3

Waterside

Free Cooling Coil

A free cooling coil constructed in a “V” frame arrangement, allowing for efficient heat transfer from the ambient air

temperature to the cooling process.
The free cooling coil is manufactured from copper tube and aluminium fin.

Free cooling is initiated whenever the outdoor ambient temperature is 2°C less than the return water temperature.

The “V” frame arrangement enables efficient concurrent cooling.
The DeltaChill Free cool chillers pipe work has been designed to optimise pressure drop. With this in mind the chiller is

more efficient in delivering a cooling solution.

Flow Proving Device

An evaporator differential pressure sensor facilitates low flow limiting and pressure drop monitoring via the

microprocessor shall be fitted to ensure a correct unit water flow.

Pump Interlock

Provision for a pump interlock is available within the control panel.

Water Flow Switch

A water flow switch is fitted ensuring integrity of the cooling solution flow

Water Filter

Water filters are fitted to protect the evaporator from clogging by sediment. This is a standard feature with the DeltaChill

Free cool.

For standard Air Cooled DeltaChill the water filter is an optional extra

CAUTION

The water flow switch or pump interlock must be fitted in addition to the flow proving device to validate warranty.

Water Connections

Water inlet and outlet connections are of a grooved and clamped type construction. The unit is supplied with a counter

pipe and coupling assembly for quick connection.
Optional flanged connections available on request, please consult Airedale.