Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 180: Dcc performance data ac fans

Advertising
background image

180

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

146

DCC051DX-12EYY0

5

535.2

137.4

508.0

151.5

478.1

167.9

445.6

186.4

6

550.9

138.2

523.1

152.4

492.3

168.8

458.9

187.3

7

566.8

139.1

538.3

153.3

506.7

169.7

472.5

188.3

8

582.8

139.9

553.6

154.2

521.4

170.6

486.3

189.3

9

598.9

140.8

569.1

155.1

536.1

171.6

500.2

190.3

10

615.2

141.7

584.8

156.0

549.7

173.0

514.4

191.3

147

DCC053DX-11DYV0

5

561.4

148.3

531.3

163.9

498.3

181.7

462.7

202.0

6

577.6

149.3

546.1

165.1

512.9

182.8

476.4

203.1

7

594.1

150.3

562.4

166.0

527.7

184.0

490.2

204.3

8

610.6

151.4

578.2

167.1

542.6

185.1

504.2

205.6

9

627.4

152.4

594.2

168.2

557.7

186.3

518.4

206.8

10

644.3

153.5

610.3

169.3

573.0

187.5

532.8

208.1

148

DCC056DX-12DVV0

5

595.8

154.7

564.0

170.9

529.1

189.5

491.5

210.8

6

613.1

155.7

580.5

171.9

544.7

190.6

506.0

212.0

7

630.7

156.7

597.2

173.0

560.5

191.7

520.8

213.2

8

648.4

157.7

614.1

174.0

576.4

192.9

535.8

214.4

9

666.3

158.7

631.1

175.2

592.6

194.1

551.0

215.7

10

684.4

159.8

648.4

176.3

609.0

195.3

566.4

216.9

149

DCC058DX-12DVW0

5

621.3

164.9

587.7

181.7

550.7

200.9

510.7

222.8

6

639.1

166.0

604.6

182.9

566.6

202.2

525.5

224.1

7

657.1

167.2

621.7

184.2

582.7

203.6

540.5

225.5

8

675.2

168.4

638.9

185.4

599.0

204.9

555.7

227.0

9

693.6

169.6

656.4

186.8

615.4

206.3

571.2

228.4

10

712.0

170.8

674.0

188.1

632.1

207.8

586.8

229.9

150

DCC061DX-12DWW0

5

658.1

175.8

621.4

193.2

581.1

213.1

537.6

235.5

6

676.7

177.1

639.0

194.7

597.6

214.6

552.9

237.1

7

695.6

178.5

656.8

196.2

614.3

216.2

568.4

238.7

8

714.6

179.9

674.8

197.7

631.2

217.8

584.1

240.3

9

733.8

181.4

693.0

199.3

648.3

219.5

600.1

242.0

10

753.1

182.9

711.4

200.8

665.6

221.1

616.2

243.7

151

DCC050DX-14EPV0

5

528.2

129.9

502.5

142.7

473.9

157.4

442.6

174.3

6

543.7

130.6

517.4

143.4

488.1

158.1

455.9

175.1

7

559.4

131.2

532.5

144.1

502.5

158.9

469.5

175.9

8

575.2

131.9

547.8

144.8

517.1

159.7

483.3

176.7

9

591.1

132.5

563.2

145.5

531.8

160.4

497.3

177.5

10

607.1

133.2

578.7

146.2

546.7

161.2

511.4

178.3

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

DCC Performance Data AC Fans

Advertising
This manual is related to the following products: