Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 71: Dcf performance data ac fans
71
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
78 DCF073TX-16GPPY
6
732.3
187.4
692.3
206.0
649.0
227.2
602.3
251.1
7
753.5
188.7
712.5
207.4
667.9
228.6
619.9
252.6
8
775.0
190.0
732.9
208.8
687.1
230.1
637.7
254.1
10
818.8
192.8
774.4
211.7
726.2
233.2
674.3
257.3
12
863.4
195.6
816.9
214.8
766.3
236.4
711.8
260.6
14
909.0
198.6
860.3
217.9
807.3
239.7
750.3
264.1
79 DCF079TX-15GYYY
6
805.2
220.9
759.0
244.1
709.4
270.4
656.3
299.8
7
828.2
222.7
780.8
245.9
729.7
272.3
675.1
301.8
8
851.4
224.5
802.8
247.8
750.4
274.3
694.3
303.9
10
898.8
228.2
847.5
251.7
792.3
278.4
733.4
308.1
12
947.0
232.1
893.2
255.9
835.3
282.6
773.6
312.5
14
996.1
236.2
939.8
260.2
879.2
287.1
814.7
317.2
80 DCF082TX-16HYYV
6
832.5
226.9
786.5
250.7
736.6
277.9
682.8
308.6
7
856.0
228.6
808.8
252.5
757.5
279.8
702.3
310.6
8
879.8
230.3
831.4
254.4
778.8
281.8
722.2
312.6
10
928.0
233.9
877.2
258.2
822.0
285.8
762.6
316.8
12
977.1
237.6
924.0
262.2
866.2
290.0
804.2
321.2
14
1026.8
241.5
971.5
266.3
911.3
294.4
846.7
325.8
81 DCF078TX-17GPYY
6
786.1
200.7
743.0
220.9
696.4
244.0
646.3
270.1
7
809.0
202.1
764.7
222.4
716.8
245.5
665.4
271.7
8
832.2
203.5
786.8
223.9
737.6
247.1
684.7
273.3
10
879.5
206.4
831.7
227.0
779.9
250.4
724.2
276.7
12
927.9
209.5
877.6
230.2
823.2
253.8
764.9
280.2
14
977.1
212.7
924.5
233.6
867.6
257.3
806.6
283.8
82 DCF082TX-18GYYY
6
828.3
213.2
783.3
235.1
734.8
260.1
682.7
288.4
7
852.5
214.7
806.3
236.6
756.4
261.7
702.9
290.1
8
877.0
216.2
829.6
238.2
778.4
263.4
723.4
291.7
10
926.9
219.2
877.1
241.4
823.2
266.7
765.3
295.2
12
977.9
222.5
925.7
244.8
869.1
270.2
808.5
298.9
14
1029.8
225.9
975.2
248.3
916.1
273.9
852.7
302.7
83 DCF085TX-17HYVV
6
859.5
232.8
812.8
257.3
761.8
285.3
706.8
317.1
7
883.8
234.4
835.8
259.1
783.6
287.2
727.1
319.1
8
908.3
236.1
859.2
260.9
805.6
289.1
747.6
321.1
10
958.1
239.6
906.6
264.6
850.3
293.1
789.6
325.3
12
1008.7
243.2
954.9
268.5
896.1
297.2
832.7
329.6
14
1059.9
246.9
1003.9
272.5
942.7
301.5
876.8
334.1
84 DCF089TX-18HVVV
6
903.5
239.8
853.9
264.9
800.1
293.8
742.0
326.6
7
929.2
241.4
878.3
266.7
823.0
295.7
763.4
328.6
8
955.3
243.1
903.1
268.5
846.3
297.6
785.1
330.7
10
1008.2
246.6
953.3
272.3
893.7
301.7
829.6
334.9
12
1062.1
250.3
1004.7
276.2
942.3
305.8
875.2
339.4
14
1116.9
254.1
1056.9
280.3
991.8
310.2
921.9
344.0
1
Output kW refers to the chilled water duty (Based upon 20% Ethylene Glycol).
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCF Performance Data AC Fans