Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 71: Dcf performance data ac fans

Advertising
background image

71

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

78 DCF073TX-16GPPY

6

732.3

187.4

692.3

206.0

649.0

227.2

602.3

251.1

7

753.5

188.7

712.5

207.4

667.9

228.6

619.9

252.6

8

775.0

190.0

732.9

208.8

687.1

230.1

637.7

254.1

10

818.8

192.8

774.4

211.7

726.2

233.2

674.3

257.3

12

863.4

195.6

816.9

214.8

766.3

236.4

711.8

260.6

14

909.0

198.6

860.3

217.9

807.3

239.7

750.3

264.1

79 DCF079TX-15GYYY

6

805.2

220.9

759.0

244.1

709.4

270.4

656.3

299.8

7

828.2

222.7

780.8

245.9

729.7

272.3

675.1

301.8

8

851.4

224.5

802.8

247.8

750.4

274.3

694.3

303.9

10

898.8

228.2

847.5

251.7

792.3

278.4

733.4

308.1

12

947.0

232.1

893.2

255.9

835.3

282.6

773.6

312.5

14

996.1

236.2

939.8

260.2

879.2

287.1

814.7

317.2

80 DCF082TX-16HYYV

6

832.5

226.9

786.5

250.7

736.6

277.9

682.8

308.6

7

856.0

228.6

808.8

252.5

757.5

279.8

702.3

310.6

8

879.8

230.3

831.4

254.4

778.8

281.8

722.2

312.6

10

928.0

233.9

877.2

258.2

822.0

285.8

762.6

316.8

12

977.1

237.6

924.0

262.2

866.2

290.0

804.2

321.2

14

1026.8

241.5

971.5

266.3

911.3

294.4

846.7

325.8

81 DCF078TX-17GPYY

6

786.1

200.7

743.0

220.9

696.4

244.0

646.3

270.1

7

809.0

202.1

764.7

222.4

716.8

245.5

665.4

271.7

8

832.2

203.5

786.8

223.9

737.6

247.1

684.7

273.3

10

879.5

206.4

831.7

227.0

779.9

250.4

724.2

276.7

12

927.9

209.5

877.6

230.2

823.2

253.8

764.9

280.2

14

977.1

212.7

924.5

233.6

867.6

257.3

806.6

283.8

82 DCF082TX-18GYYY

6

828.3

213.2

783.3

235.1

734.8

260.1

682.7

288.4

7

852.5

214.7

806.3

236.6

756.4

261.7

702.9

290.1

8

877.0

216.2

829.6

238.2

778.4

263.4

723.4

291.7

10

926.9

219.2

877.1

241.4

823.2

266.7

765.3

295.2

12

977.9

222.5

925.7

244.8

869.1

270.2

808.5

298.9

14

1029.8

225.9

975.2

248.3

916.1

273.9

852.7

302.7

83 DCF085TX-17HYVV

6

859.5

232.8

812.8

257.3

761.8

285.3

706.8

317.1

7

883.8

234.4

835.8

259.1

783.6

287.2

727.1

319.1

8

908.3

236.1

859.2

260.9

805.6

289.1

747.6

321.1

10

958.1

239.6

906.6

264.6

850.3

293.1

789.6

325.3

12

1008.7

243.2

954.9

268.5

896.1

297.2

832.7

329.6

14

1059.9

246.9

1003.9

272.5

942.7

301.5

876.8

334.1

84 DCF089TX-18HVVV

6

903.5

239.8

853.9

264.9

800.1

293.8

742.0

326.6

7

929.2

241.4

878.3

266.7

823.0

295.7

763.4

328.6

8

955.3

243.1

903.1

268.5

846.3

297.6

785.1

330.7

10

1008.2

246.6

953.3

272.3

893.7

301.7

829.6

334.9

12

1062.1

250.3

1004.7

276.2

942.3

305.8

875.2

339.4

14

1116.9

254.1

1056.9

280.3

991.8

310.2

921.9

344.0

1

Output kW refers to the chilled water duty (Based upon 20% Ethylene Glycol).

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

DCF Performance Data AC Fans

Advertising
This manual is related to the following products: