Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 186: Dcc performance data ec fans
![background image](/manuals/370937/186/background.png)
186
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
DCC Performance Data EC Fans
Ambient (°C)
Model
Supply Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
98
DCC047DR-08EPV0
5
504.7
138.8
479.9
152.8
452.0
168.9
420.0
186.7
6
519.3
139.8
494.0
153.9
465.1
169.9
432.3
187.7
7
534.2
140.7
508.2
154.9
478.4
171.0
444.8
188.8
8
549.1
141.8
522.6
156.0
491.8
172.0
457.5
189.8
9
564.2
142.8
537.1
157.1
505.4
173.1
470.3
190.9
10
579.4
143.8
551.8
158.2
519.2
174.2
483.3
192.1
99
DCC049DR-08EYY0
5
521.9
145.4
496.5
160.1
466.4
176.8
433.8
195.7
6
537.5
146.5
511.0
161.1
480.1
177.9
446.7
196.7
7
553.2
147.5
525.7
162.2
494.0
178.9
459.7
197.8
8
569.2
148.7
540.5
163.2
508.0
180.0
472.9
198.9
9
585.2
149.7
555.5
164.3
522.2
181.1
486.3
200.1
10
601.0
150.7
570.6
165.3
536.6
182.3
499.9
201.3
100
DCC049DR-10EPV0
5
514.6
132.5
490.6
146.3
464.4
162.4
435.1
180.4
6
529.9
133.4
505.7
147.4
478.5
163.3
448.3
181.4
7
545.1
134.3
520.7
148.3
492.9
164.3
461.8
182.3
8
560.7
135.2
535.6
149.2
507.5
165.4
475.4
183.3
9
576.5
136.1
551.2
150.3
522.3
166.4
489.3
184.3
10
592.3
137.0
566.4
151.2
537.2
167.4
503.4
185.3
101
DCC051DR-10EYY0
5
530.8
138.6
506.5
153.3
479.6
170.4
450.0
189.6
6
546.7
139.6
521.9
154.3
494.4
171.4
464.1
190.7
7
562.2
140.4
537.5
155.3
509.3
172.4
477.9
191.5
8
578.5
141.4
553.3
156.3
524.6
173.5
492.0
192.4
9
595.4
142.5
569.3
157.4
540.0
174.5
506.3
193.3
10
611.5
143.4
585.4
158.4
555.6
175.6
520.7
194.3
102
DCC052DR-09DYV0
5
560.1
151.4
533.4
167.1
502.4
184.9
467.5
204.6
6
576.8
152.5
549.3
168.1
517.2
185.9
481.4
205.7
7
593.8
153.6
565.3
169.2
532.2
187.0
495.5
206.8
8
610.9
154.7
581.6
170.3
547.5
188.0
509.8
207.9
9
628.0
155.7
598.1
171.4
562.9
189.1
524.4
209.0
10
645.2
156.8
614.7
172.6
578.4
190.3
539.1
210.2
103
DCC056DR-10DVV0
5
593.9
157.0
566.7
173.7
535.0
192.6
498.0
213.3
6
611.7
158.1
583.9
174.9
550.9
193.6
512.9
214.4
7
629.8
159.2
601.4
176.0
567.0
194.6
528.1
215.4
8
648.1
160.3
619.1
177.2
583.3
195.7
543.5
216.5
9
666.6
161.4
637.0
178.3
599.9
196.7
559.1
217.6
10
685.3
162.6
655.0
179.5
616.6
197.8
575.0
218.8
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.