Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data - regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 138

Advertising
background image

138

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

ELECTRICAL DATA

25

26

27

Unit Data

DCF062DR-14DVV0

DCF066DR-14FVW0

DCF070DR-14FWW0

Nominal Run Amps

(1)

A

409.2

421.2

433.3

Maximum Start Amps

A

617.6

656.5

668.6

Recommended Mains Fuse Size

A

450

450

500

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

14

14

14

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

14

14

14

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

14

14

14

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 55.2

55.2 / 59.2

59.2 / 59.2

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

33.1 / 33.1

33.1 / 36.2

36.2 / 36.2

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 267

267 / 298

298 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

364.3

378.5

392.6

Reactive power reduction/saving

(4)

kVAr

72.4

70.1

67.8

Maximum Start Amps

A

572.7

613.8

627.9

Recommended Mains Fuse Size

A

450

450

500

Electronic Soft-start
Nominal Run Amps

A

409.2

421.2

433.3

Maximum Start Amps

A

510.8

537.3

549.4

Recommended Mains Fuse

A

450

450

500

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

364.3

378.5

392.6

Maximum Start Amps

A

465.9

494.6

508.7

Recommended Mains Fuse Size

A

450.0

450.0

500.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

430.4

442.4

454.4

Recommended Mains Fuse Size

A

450

500

500

Motor Rating

kW

12.1

12.1

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

437.7

449.7

461.7

Recommended Mains Fuse Size

A

500

500

500

Motor Rating

kW

16.4

16.4

16.4

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

424.4

436.5

448.7

Recommended Mains Fuse Size

A

450

500

500

Motor Rating

kW

12.4

12.4

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

429.9

442.1

454.3

Recommended Mains Fuse Size

A

500

500

500

Motor Rating

kW

16.8

16.8

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet