ELECTRICAL DATA
25
26
27
Unit Data
DCF062DR-14DVV0
DCF066DR-14FVW0
DCF070DR-14FWW0
Nominal Run Amps
(1)
A
409.2
421.2
433.3
Maximum Start Amps
A
617.6
656.5
668.6
Recommended Mains Fuse Size
A
450
450
500
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
14
14
14
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
14
14
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
14
14
14
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2
55.2 / 59.2
59.2 / 59.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
33.1 / 33.1
33.1 / 36.2
36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 267
267 / 298
298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
364.3
378.5
392.6
Reactive power reduction/saving
(4)
kVAr
72.4
70.1
67.8
Maximum Start Amps
A
572.7
613.8
627.9
Recommended Mains Fuse Size
A
450
450
500
Electronic Soft-start
Nominal Run Amps
A
409.2
421.2
433.3
Maximum Start Amps
A
510.8
537.3
549.4
Recommended Mains Fuse
A
450
450
500
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
364.3
378.5
392.6
Maximum Start Amps
A
465.9
494.6
508.7
Recommended Mains Fuse Size
A
450.0
450.0
500.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
430.4
442.4
454.4
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
437.7
449.7
461.7
Recommended Mains Fuse Size
A
500
500
500
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
424.4
436.5
448.7
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
429.9
442.1
454.3
Recommended Mains Fuse Size
A
500
500
500
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet