ELECTRICAL DATA
79
80
81
Unit Data
DCF079TX-15GYYY
DCF082TX-16HYYV
DCF078TX-17GPYY
Nominal Run Amps
(1)
A
489.5
516.5
468.6
Maximum Start Amps
A
726.1
744.9
703.9
Recommended Mains Fuse Size
A
560
560
500
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
15
16
17
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
15
16
17
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5 / 47.5
47.5 / 47.5 / 55.2
59.2 / 47.5 / 47.5
Quantity
3 + 3 + 3
3 + 3 + 3
2 + 3 + 3
Motor Rating
kW
29.6 / 29.6 / 29.6
29.6 / 29.6 / 33.1
36.2 / 29.6 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287 / 287
287 / 287 / 267
298 / 287 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
459.7
478.9
436.6
Reactive power reduction/saving
(4)
kVAr
53.8
65.8
56.6
Maximum Start Amps
A
696.3
707.3
671.9
Recommended Mains Fuse Size
A
560
560
500
Electronic Soft-start
Nominal Run Amps
A
489.5
516.5
468.6
Maximum Start Amps
A
611.3
630.1
584.7
Recommended Mains Fuse
A
560
560
500
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
459.7
478.9
436.6
Maximum Start Amps
A
581.5
592.5
552.7
Recommended Mains Fuse Size
A
560
560
500
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
21.2
Unit Nominal Run Amps
A
517.8
544.9
489.7
Recommended Mains Fuse Size
A
560
630
560
Motor Rating
kW
16.4
16.4
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
28.5
Unit Nominal Run Amps
A
524.3
551.4
497.0
Recommended Mains Fuse Size
A
560
630
560
Motor Rating
kW
20.3
20.3
16.4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
19.8
Unit Nominal Run Amps
A
511.3
538.0
484.5
Recommended Mains Fuse Size
A
560
560
560
Motor Rating
kW
16.8
16.8
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
26.9
Unit Nominal Run Amps
A
516.4
543.0
490.2
Recommended Mains Fuse Size
A
560
630
560
Motor Rating
kW
20.7
20.7
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet