ELECTRICAL DATA

79

80

81

Unit Data

DCF079TX-15GYYY

DCF082TX-16HYYV

DCF078TX-17GPYY

Nominal Run Amps

(1)

A

489.5

516.5

468.6

Maximum Start Amps

A

726.1

744.9

703.9

Recommended Mains Fuse Size

A

560

560

500

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

15

16

17

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

15

16

17

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5 / 47.5

47.5 / 47.5 / 55.2

59.2 / 47.5 / 47.5

Quantity

3 + 3 + 3

3 + 3 + 3

2 + 3 + 3

Motor Rating

kW

29.6 / 29.6 / 29.6

29.6 / 29.6 / 33.1

36.2 / 29.6 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287 / 287

287 / 287 / 267

298 / 287 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

459.7

478.9

436.6

Reactive power reduction/saving

(4)

kVAr

53.8

65.8

56.6

Maximum Start Amps

A

696.3

707.3

671.9

Recommended Mains Fuse Size

A

560

560

500

Electronic Soft-start
Nominal Run Amps

A

489.5

516.5

468.6

Maximum Start Amps

A

611.3

630.1

584.7

Recommended Mains Fuse

A

560

560

500

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

459.7

478.9

436.6

Maximum Start Amps

A

581.5

592.5

552.7

Recommended Mains Fuse Size

A

560

560

500

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

21.2

Unit Nominal Run Amps

A

517.8

544.9

489.7

Recommended Mains Fuse Size

A

560

630

560

Motor Rating

kW

16.4

16.4

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

28.5

Unit Nominal Run Amps

A

524.3

551.4

497.0

Recommended Mains Fuse Size

A

560

630

560

Motor Rating

kW

20.3

20.3

16.4

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

19.8

Unit Nominal Run Amps

A

511.3

538.0

484.5

Recommended Mains Fuse Size

A

560

560

560

Motor Rating

kW

16.8

16.8

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

26.9

Unit Nominal Run Amps

A

516.4

543.0

490.2

Recommended Mains Fuse Size

A

560

630

560

Motor Rating

kW

20.7

20.7

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet