DeltaChill™Air Cooled and FreeCool
Installation Data
Positioning
The installation position should be selected with the following points in mind:
•
Position on a stable and even base, levelled to ensure that the compressor operates correctly
•
Levelling should be to +/- 5mm
•
Where vibration transmission to the building structure is possible, fit spring anti-vibration mounts and flexible
water connections
•
Observe airflow and maintenance clearance
•
Pipework and electrical connections are readily accessible
•
Where multiple units are installed, due care should be taken to avoid the discharge air from each unit adversely
affecting other units in the vicinity
•
Within a side enclosed installation, the fan
MUST be higher than the enclosing structure
•
Increase airflow and maintenance clearances for side-enclosed or multiple unit applications.
•
Allow free space above the fans to prevent air recirculation
•
Ensure that there is a safe access and operating area provided for unit controls
CAUTION
Prior to connecting services, ensure that the equipment is installed and completely level.
Airflow & Maintenance Clearances
A
A
B
C
D
Application
Distance from Overall Base Dimension (mm)
A
B
C
D
Free of walls and overhang
1300
1300
1300
1300
Enclosed to A
2600
1300
1300
1300
Unit parallel with A
2600
1300
1300
1300
Enclosed to B
1300
2600
1300
1300
Unit in line with B
1300
1300
1300
1300
Unit in line with C Controls End
1300
1300
2600
1300
Enclosed to C
1300
1300
2600
1300