Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 244: Dcc electrical data - regular quiet

Advertising
background image

244

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

140

141

142

Unit Data

DCC090TR-21GVVW

DCC093TR-21GVWW

DCC096TR-21GWWW

Nominal Run Amps

(1)

A

625.8

637.8

649.9

Maximum Start Amps

A

861.1

873.1

885.2

Recommended Mains Fuse Size

A

670

670

710

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

21

21

21

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

21

21

21

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 55.2 / 59.2

55.2 / 59.2 / 59.2

59.2 / 59.2 / 59.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

33.1 / 33.1 / 36.2

33.1 / 36.2 / 36.2

36.2 / 36.2 / 36.2

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 267 / 298

267 / 298 / 298

298 / 298 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

560.6

574.8

588.9

Reactive power reduction/saving

(4)

kVAr

106.3

104.0

101.8

Maximum Start Amps

A

795.9

810.1

824.2

Recommended Mains Fuse Size

A

670

670

710

Electronic Soft-start
Nominal Run Amps

A

625.8

637.8

649.9

Maximum Start Amps

A

741.9

753.9

766.0

Recommended Mains Fuse

A

670

670

710

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

560.6

574.8

588.9

Maximum Start Amps

A

676.7

690.9

705.0

Recommended Mains Fuse Size

A

670

670

710

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

15.2

15.2

15.2

Unit Nominal Run Amps

A

640.9

652.9

665.0

Recommended Mains Fuse Size

A

670

710

710

Motor Rating

kW

8.4

8.4

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

647.0

659.0

671.1

Recommended Mains Fuse Size

A

670

710

710

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

13.9

Unit Nominal Run Amps

A

636.4

648.5

660.7

Recommended Mains Fuse Size

A

670

710

710

Motor Rating

kW

8.6

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

641.1

653.2

665.3

Recommended Mains Fuse Size

A

670

710

710

Motor Rating

kW

12.4

12.4

12.4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Regular Quiet

Advertising
This manual is related to the following products: