Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 228: Dcc mechanical data - extra quiet

Advertising
background image

228

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

179

180

181

182

DCC085TX-21GVVV

DCC088TX-21GVVW

DCC091TX-21GVWW

DCC094TX-21GWWW

FreeCooling

N

N

N

N

Enhance Capital Allowance

N

N

N

N

Number of Refrigeration Circuits

2

2

2

2

Cooling Duty - High Airflow EC Fans
Nominal Output - Mechanical

(1)

kW

N/A

N/A

N/A

N/A

Nominal Input - Mechanical

kW

N/A

N/A

N/A

N/A

EER

(2)

N/A

N/A

N/A

N/A

ESEER

N/A

N/A

N/A

N/A

SEER

N/A

N/A

N/A

N/A

Nominal Output - Free Cooling

kW

N/A

N/A

N/A

N/A

Ambient temperature for 100% Free Cooling

(5)

°C

N/A

N/A

N/A

N/A

Cooling Duty - EC Fans
Nominal Output - Mechanical

(1)

kW

845.1

879.2

906.2

933.2

Nominal Input - Mechanical

kW

272.3

284.3

295.8

307.3

EER

(2)

3.10

3.09

3.06

3.04

ESEER

4.55

4.59

4.55

4.51

SEER

4.39

4.42

4.39

4.34

Nominal Output - Free Cooling

kW

Ambient temperature for 100% Free Cooling

(5)

°C

Cooling Duty - AC Fans
Nominal Output - Mechanical

(1)

kW

847.8

882.3

909.5

936.7

Nominal Input - Mechanical

kW

279.0

290.9

302.3

313.7

EER

(2)

3.04

3.03

3.01

2.99

ESEER

4.16

4.19

4.18

4.15

SEER

4.04

4.07

4.05

4.03

Nominal Output - Free Cooling

kW

Ambient temperature for 100% Free Cooling

(5)

°C

Capacity Steps

%

10-25-35-45-55-

70-80-90-100

10-20-35-45-55-

70-80-90-100

10-25-35-45-55-

70-80-90-100

10-25-35-45-60-

70-80-90-100

Minimum Turndown Ratio

0.11

0.11

0.11

0.12

Dimensions (H x W x L)

mm

2682 x 2200 x 12770

2682 x 2200 x 12770

2682 x 2200 x 12770

2682 x 2200 x 12770

Weight
Machine

(3)

kg

8135

8185

8215

8245

Operating

kg

8905

8950

8975

9005

Water Volume (Total Internal)

l

770

765

760

760

Maximum Waterflow

l/s

46.1

63.1

63.1

63.1

Minimum Waterflow

l/s

17.7

14.1

14.1

14.1

Face Area (Total)

2.38

2.38

2.38

2.38

Nominal Airflow - High Airflow EC Fans

m³/s

N/A

N/A

N/A

N/A

Nominal Airflow - EC Fans

m³/s

92.7

92.7

92.7

92.7

Nominal Airflow - AC Fans

m³/s

95.6

95.6

95.6

95.6

Quantity

21

21

21

21

Maximum Speed - High Airflow EC Fans

rpm

N/A

N/A

N/A

N/A

Maximum Speed - EC Fans

rpm

725

725

725

725

Maximum Speed - AC Fans

rpm

733

733

733

733

Compressor

Trio + Trio + Trio

Trio + Trio + Trio

Trio + Trio + Trio

Trio + Trio + Trio

Quantity of Compressors

9

9

9

9

Oil Charge Volume (Total)

l

3 x 5.3 + 3 x 5.3 + 3 x 5.33 x 5.3 + 3 x 5.3 + 3 x 5.33 x 5.3 + 3 x 5.3 + 3 x 5.33 x 5.3 + 3 x 5.3 + 3 x 5.3

Refrigeration
Charge (Total)

kg

39 + 39 + 42

40 + 40 + 44

40 + 40 + 44

40 + 40 + 44

Water Inlet / Outlet - Unit

DN150

DN150

DN150

DN150

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System
Minimum System Water Volume

(4)

l

6577

6831

7019

7359

Maximum System Operating Pressure

Bar

10

10

10

10

(1)

Based on units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water.

(2)

EER = DX Cooling Output / (Compressor input power + Fan Input Power),

(3)

Based on standard unit without options, operating weight includes refrigerant charge and water volume.

For unit weights with waterside options fitted please refer to Airedale.

(4)

For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations

(5)

Ambient temperature that full Freecool capacity can be achieved