Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 159: Dcf electrical data extra quiet

Advertising
background image

159

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

88

89

90

Unit Data

DCF074TX-19GPPY

DCF079TX-20GPYY

DCF085TX-19HYYV

Nominal Run Amps

(1)

A

447.8

475.9

523.8

Maximum Start Amps

A

683.1

711.2

752.2

Recommended Mains Fuse Size

A

500

500

560

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

19

20

19

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

19

20

19

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 59.2 / 47.5

59.2 / 47.5 / 47.5

47.5 / 47.5 / 55.2

Quantity

2 + 2 + 3

2 + 3 + 3

3 + 3 + 3

Motor Rating

kW

36.2 / 36.2 / 29.6

36.2 / 29.6 / 29.6

29.6 / 29.6 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 298 / 287

298 / 287 / 287

287 / 287 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

413.6

442.4

484.7

Reactive power reduction/saving

(4)

kVAr

59.3

58.9

68.1

Maximum Start Amps

A

648.9

677.7

713.1

Recommended Mains Fuse Size

A

500

500

560

Electronic Soft-start
Nominal Run Amps

A

447.8

475.9

523.8

Maximum Start Amps

A

563.9

592.0

637.4

Recommended Mains Fuse

A

500

500

560

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

413.6

442.4

484.7

Maximum Start Amps

A

529.7

558.5

598.3

Recommended Mains Fuse Size

A

500

500

560

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

28.5

Unit Nominal Run Amps

A

468.9

496.9

552.2

Recommended Mains Fuse Size

A

500

560

630

Motor Rating

kW

12.1

12.1

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

35.0

Unit Nominal Run Amps

A

476.2

504.2

558.7

Recommended Mains Fuse Size

A

500

560

630

Motor Rating

kW

16.4

16.4

20.3

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

26.9

Unit Nominal Run Amps

A

463.6

491.7

545.2

Recommended Mains Fuse Size

A

500

560

630

Motor Rating

kW

12.4

12.4

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

33.2

Unit Nominal Run Amps

A

469.2

497.4

550.2

Recommended Mains Fuse Size

A

500

560

630

Motor Rating

kW

16.8

16.8

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet