Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 159: Dcf electrical data extra quiet
159
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
88
89
90
Unit Data
DCF074TX-19GPPY
DCF079TX-20GPYY
DCF085TX-19HYYV
Nominal Run Amps
(1)
A
447.8
475.9
523.8
Maximum Start Amps
A
683.1
711.2
752.2
Recommended Mains Fuse Size
A
500
500
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
19
20
19
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
19
20
19
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 59.2 / 47.5
59.2 / 47.5 / 47.5
47.5 / 47.5 / 55.2
Quantity
2 + 2 + 3
2 + 3 + 3
3 + 3 + 3
Motor Rating
kW
36.2 / 36.2 / 29.6
36.2 / 29.6 / 29.6
29.6 / 29.6 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 298 / 287
298 / 287 / 287
287 / 287 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
413.6
442.4
484.7
Reactive power reduction/saving
(4)
kVAr
59.3
58.9
68.1
Maximum Start Amps
A
648.9
677.7
713.1
Recommended Mains Fuse Size
A
500
500
560
Electronic Soft-start
Nominal Run Amps
A
447.8
475.9
523.8
Maximum Start Amps
A
563.9
592.0
637.4
Recommended Mains Fuse
A
500
500
560
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
413.6
442.4
484.7
Maximum Start Amps
A
529.7
558.5
598.3
Recommended Mains Fuse Size
A
500
500
560
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
28.5
Unit Nominal Run Amps
A
468.9
496.9
552.2
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
12.1
12.1
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
35.0
Unit Nominal Run Amps
A
476.2
504.2
558.7
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
16.4
16.4
20.3
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
26.9
Unit Nominal Run Amps
A
463.6
491.7
545.2
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
12.4
12.4
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
33.2
Unit Nominal Run Amps
A
469.2
497.4
550.2
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
16.8
16.8
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet