7–5

Communicating with an SLC on a DH-485 Network

Publication 2755-6.8

Connecting Readers to SLC 5/04 Controller – 2 AIC Modules

The SLC 5/04 controller requires two 1747-PIC converters and a
power supply to connect to the second 1747-AIC module.

The end devices on a DH-485 network must be terminated. The
wiring base of the AdaptaScan Reader provides a termination switch.

SLC 5/04 Processor

Term
A
B
Com
Shield
Chassis Gnd

1747-PIC

1747-AIC Module

Term
A
B
Com
Shield
Chassis Gnd

1747-AIC Module

1747-P4

24V dc Power Supply

1747-PIC

AdaptaScan Wiring Base

RS-422/RS-485 Terminal

AdaptaScan Wiring Base

RS-422/RS-485 Terminal

Computer

The 1747-P4 Power Supply provides
power to both 1747-AIC modules (1 AMP,
24V dc). Otherwise use 2 power supplies.

DH-485

RS-232

RS-232

DH-485

Channel 0

Power

Supply