Making devicenet connections – Rockwell Automation 2755-SNx Adaptascan Bar Code Readers User Manual

Page 326

Advertising
background image

17–4

Communicating with PanelView 900

t

Terminals on a DeviceNet Network

Publication 2755-6.8

Use DeviceNet cable to connect a DeviceNet version of a PanelView
terminal to a DeviceNet Network.

Cable

Catalog No.

DeviceNet Cable, 164 ft (50m)

1485C-P1A50

DeviceNet Cable, 328 ft (100m)

1485C-P1A150

DeviceNet Cable, 492 ft (150m)

1485C-P1A300

Important: Refer to the DeviceNet Cable System Planning and
Installation Manual
(Publication No. 1485-6.7.1) for network layout
and design information.

DeviceNet Port

PanelView 900 Terminal

Catalog Number 2711-K9A10, -T9A10, K9C10, -T9C10

5

1

DeviceNet

Terminal Block

Terminal

Signal

Function

Color

1

COM

Common

Black

1

2

CAN_L

Signal Low

Blue

1

3

SHIELD

Shield

Uninsulated

4

CAN_H

Signal High

White

5

5

VDC+

Power Supply

Red

Making DeviceNet
Connections

Advertising