Communicating with PanelView 900

t

Terminals on a DeviceNet Network

Publication 2755-6.8

Configuring DeviceNet Communications

DeviceNet communication parameters are accessed from the
Terminal Setup dialog. To open the Terminal Setup dialog, choose
Terminal Setup from the PanelBuilder Application menu.

7. Click the Comms. Setup button from the Terminal Setup dialog.

8. Under Terminal, edit the following parameters:

Specify

To

Node Address

Select the address (0 to 63) of the PanelView
terminal on the DeviceNet link.

Baud Rate

Select the baud rate of the DeviceNet link. The
available baud rates are:

125 kbps
250 kbps
500 kbps

9. Under I/O Scanner, edit the following parameters:

Specify

To

Input Size

Specify the number of words (from 0 to 64) that
are sent to the scanner from the PanelView with
each I/O message. 0 is the default value which
indicates that no input I/O data exists in the
application.

Output Size

Specify the number of words (from 0 to 64) that
are received by the PanelView from the scanner
with each I/O message. 0 is the default value
which indicates that no output I/O data exists in
the application.