11–4

Communicating with a PLC-5 Processor on a DeviceNet Network

Publication 2755-6.8

Message Flow Control

DeviceNet Input #8 and Output #16 control the transmission of bar
code messages when using DeviceNet master-slave. Message flow
control (handshaking) lets the controller know that data is available
and that the reader does not send out messages faster than they can
be received. Your controller logic program must transfer the
message data and set the DeviceNet Input #8 (Send Next Data) for
message flow control.

New Data

Is indicated by changing the state of DeviceNet Output #16 of the
DeviceNet I/O. A change of state (0 to 1 or 1 to 0) indicates that a
new message is being sent.

Send Next Data

Is indicated by changing the state of DeviceNet Input #8 of the
DeviceNet I/O. A change of state (0 to 1 or 1 to 0) indicates that the
controller is ready to receive the next message.

Flow Control Example

The following shows how DeviceNet Input #8 and Output #16
control the transmission of messages. Output #16 is changed by the
reader and Input #8 is changed by the controller.

DeviceNet Scan Number

Message Data

DeviceNet

Output #16

DeviceNet

Input #8

1 - Poll

-

OFF (0)

1 - Response

No Message Sent

OFF (0)

2 - Poll

-

ON (1)

2 - Response

Message 1 Sent

ON (1)

3 - Poll

-

OFF (0)

3 - Response

Message 2 Sent

OFF (0)